D-500 MK3 User Manual Firmware V-7.5
- 138 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
Peak Lopping Start
Power
kW
0
65000
80
In
peak lopping
mode the multi genset
system will start and enter in parallel with
the mains only if the mains power
exceeds this limit. However it will supply
power to the load only if the load power
exceeds
Peak Lopping Maximum Mains
Power
parameter. This parameter should
be set lower than
Peak Lopping
Maximum Mains Power
parameter.
Power Export Enable
-
0
1
0
0: Normal operation.
1: Power Export to Mains operation.
Exported Power
kW
0
65000
100
This is the active power to be exported to
the mains in Power Export to Mains
operation mode
Exported Power Factor
-
0.600
-0.600
1.000
This is the power factor of the power
exported to the mains in Power Export to
Mains operation mode.
Command Active Power
G Gain
%
0
200
10
This parameter governs the active power
catching speed of the synchronization
unit.
If this parameter is increased, the
operation will be faster but unstable. If it
is decreased, the operation will be slower
but more stable. The best setting is the
fastest stable operation.
Command Reactive
Power G Gain
%
0
200
20
This parameter governs the reactive
power catching speed of the
synchronization unit.
If this parameter is increased, the
operation will be faster but unstable. If it
is decreased, the operation will be slower
but more stable. The best setting is the
fastest stable operation.
Minimum Exported
Power
kW
0
65000
100
In the
Distributed Power Export to
Mains
mode, the exported power will not
fall below this limit.
Export Power Ramp
(kW/sec)
%
0
100.0
1.0
In the Distributed Power Export to Mains
mode, the genset active export power
(KW) will be increased/decreased with
this rate.
Frequency Barrier
Hz
0.1
2.0
0.5
In the Distributed Power Export to Mains
mode, this is the minimum variation from
the nominal frequency causing an active
power rump-up or ramp-down.
Speed Up/Down
Pulse Minimum
msec
10
200
10
This parameter defines the minimum
pulse width in speed pulse control mode.
Speed Up/Down
Pulse Maximum Duration
msec
0
2000
0
This parameter defines the maximum
pulse width in speed pulse control mode.
If this parameter is set to zero then no
maximum pulse width is used.
Speed Up/Down
Pulse Delay
msec
20
1000
20
This parameter defines the minimum
pulse delay between two speed up/down
control pulses.
Voltage Up/Down
Pulse Minimum
msec
10
200
10
This parameter defines the minimum
pulse width in voltage pulse control mode.
Содержание D-500 MK3
Страница 40: ...D 500 MK3 User Manual Firmware V 7 5 40 5 3 3 PHASE 3 WIRE DELTA 5 2 3 PHASE 4 WIRE STAR ...
Страница 41: ...D 500 MK3 User Manual Firmware V 7 5 41 5 4 3 PHASE 4 WIRE DELTA 5 5 3 PHASE 3 WIRE DELTA 2 CT L1 L2 ...
Страница 43: ...D 500 MK3 User Manual Firmware V 7 5 43 5 9 1 PHASE 2 WIRE 5 8 2 PHASE 3 WIRE DELTA 2 CTs L1 L3 ...
Страница 53: ...D 500 MK3 User Manual Firmware V 7 5 53 7 1 GENSET SYNCHRONIZATION FUNCTIONALITY 7 CONNECTION DIAGRAMS ...
Страница 54: ...D 500 MK3 User Manual Firmware V 7 5 54 7 2 MAINS SYNCHRONIZATION FUNCTIONALITY ...
Страница 55: ...D 500 MK3 User Manual Firmware V 7 5 55 7 3 SINGLE GENSET PARALLEL WITH MAINS FUNCT ...
Страница 56: ...D 500 MK3 User Manual Firmware V 7 5 56 7 4 AMF FUNCTIONALITY ...
Страница 57: ...D 500 MK3 User Manual Firmware V 7 5 57 7 5 ATS FUNCTIONALITY ...
Страница 58: ...D 500 MK3 User Manual Firmware V 7 5 58 7 6 REMOTE START FUNCTIONALITY ...
Страница 59: ...D 500 MK3 User Manual Firmware V 7 5 59 7 7 ENGINE CONTROL FUNCTIONALITY ...
Страница 60: ...D 500 MK3 User Manual Firmware V 7 5 60 7 8 REMOTE DISPLAY PANEL FUNCTIONALITY ...
Страница 72: ...D 500 MK3 User Manual Firmware V 7 5 72 ...