Data Industrial Series 340 Btu transmitter Owner’s Manual

3

Se

ns

or

 In

pu

t

Power Out
Signal 

+

Signal 

-

Shield

Te

m

p 2

Te

m

p 1

Mod

S/N 3

Input LED

Mattapoisett, MA

Red

Black

Shield
(if applicable)

Series 200

or 

SDI

Po

w

er I

n

AC L/DC 

+

AC C/DC

-

Ou
tp

ut

Pulse Out

-

Pulse Out

+

Output LED

Input LED

DC +

or

AC Load

DC -

or

AC Common

Earth
Ground

AC or DC

Power Supply

Temperature Sensor Installation

The location of the temperature sensors with regard to the flow
sensor is important to the accuracy of the energy calculation.
Temperature sensor 

T1

 must be located closest to the flow

sensor. A distance of 5 pipe diameters will give the greatest
accuracy. Always install the temperature sensor downstream
of the flow sensor.

Electrical Installation

All connections to the 340 are made to screw terminals on
removable headers.

Power Supply Wiring

The Series 340 requires 12-24 Volts AC or DC to
operate. The power connections are made to the
ORANGE header.  The connections are labeled beside
the header.  Observe the polarity shown on the label.

If a Data Industrial plug in type power supply
(A-1026 or A-503) is used connect the black/white
striped wire to the terminal marked positive (+) and the
black wire to the terminal marked negative (-).

Note:
Included with every Series 340 is a 340IK kit
containing a screw, lock washer and nut to connect
the Series 340 to Earth Ground.  Connect the Earth
Ground Lug of the Series 340 to a solid Earth

Ground with as short a wire as possible. This will help prevent electrical interference from
affecting the Series 340’s normal operation.

Sensor Wiring

All flow sensor types connect to the four terminal
header labeled “Sensor Input”.

200 Series and M Series

Connect the Red wire to Sensor signal (+), Black
wire to Sensor signal (-) and the Bare wire to
Shield.

SDI Series

Connect the Plus (+) terminal of the sensor to
Sensor signal (+) on the transmitter and the Minus
(-) terminal of the sensor to Sensor signal (-) on
the transmitter. Connect the shield terminal of the
sensor to the shield terminal of the transmitter.

Other Flow Sensors

The Sensor Input 

Power Out

 terminal supplies

nominal 12VDC excitation voltage for 3 wire sensors. Connect sensor 

 and sensor 

signal -

wires to transmitter terminals.

Sample Sensor Wiring

Diagram

Side View - Typical 300 Series
Removable Connector Wiring

3/32” Flathead 
Screwdriver

Series 300
Connector

Wire

Sample Power Supply Wiring

Diagram

Содержание 340 Series

Страница 1: ...puter real time flow rate flow total both temperature readings energy rate and energy total are available The Series 340 transmitter features two LED s to verify input and output signals The standard output for the Series 340 is an isolated solid state switch closure that is user programmed for units of energy or flow The output pulse width is adjustable from 50 mS to 5 sec The Series 340 Btu tran...

Страница 2: ...ment of the programming cable The unit generates very little heat so no consideration need be given to cooling or ventilation Surface Mount Installation The 340 may be mounted to the surface of any panel using double sided adhesive tape or by attaching fasteners through the holes in the mounting flanges of the unit Din rail Mounting Optional clips snap onto the mounting flanges allowing the 340 to...

Страница 3: ...is used connect the black white striped wire to the terminal marked positive and the black wire to the terminal marked negative Note Included with every Series 340 is a 340IK kit containing a screw lock washer and nut to connect the Series 340 to Earth Ground Connect the Earth Ground Lug of the Series 340 to a solid Earth Ground with as short a wire as possible This will help prevent electrical in...

Страница 4: ...rve the electrical polarity of the output Communications cable wiring Field calibration requires a Data Industrial A340 Programming kit consisting of a custom cable and software and a PC running Windows 9x ME NT or 2000 In order to calibrate the Series 340 must be connected to power and the A301 cable must be connected to the 340 Comm port connector and an available 9 pin COM port on a computer No...

Страница 5: ...ustrial A 301 communications cable to the socket labeled D I C Comm Port taking care to properly align the tab on the plug and socket to maintain polarity Connect the DB9 connector of the Data Industrial A301 communications cable to a PC com port that has the 340 software installed 3 Connect the Series 340 transmitter to a power supply 4 Open the interface software and select the appropriate COM P...

Страница 6: ...ed with 10 providing the greatest degree of smoothing See the Dialog Box below 6 Program using diagram below as a reference Step 1 see note 1 Select the flow sensor type sine or pulse and enter the k and offset Step 4 Select the desired flow rate and total units here Step 7 Press send to transmit calibration data to the 340 Step 5 Select the desired energy rate and total units here Step 2 Select t...

Страница 7: ...ce Opto isolated solid state switch Operating Voltage range 0 60V DC or AC peak Closed on state Load Current 700mA max over operating temperature range On resistance 700mΩ max over operating temperature range Open off state leakage 70 C 1 A 60V DC or AC peak Operating Temperature 29 C to 70 C 20 F to 158 F Storage Temperature 40 C to 85 C 40 F to 185 F Weight 4 8 oz With headers installed SENSOR C...

Страница 8: ... a Version n a Temperature Units F Sensor Type Pulse K 1 offset 0 Flow Rate Units gpm Flow Total Units gallons Energy Rate Units kBtu hr Energy Total Units Btu Energy Calculation absolute Flow Filter 0 Energy Filter 0 Scaled Pulse Output Units energy Scaled Pulse Output Units Per Pulse 1 Scaled Pulse Output Pulse Width 100 ...

Страница 9: ...ress Seller may at its sole option instruct Buyer to ship subject part postage prepaid to the Seller at above address or authorize a representative to inspect the part on site Seller will at its sole option repair or replace any defective product covered by this warranty If Buyer makes repairs or alterations to any product or part covered by this warranty without Sellers prior written approval thi...

Отзывы: