29
Maintenance and care
: User Rights
en
Drain and hose must be checked every year.
Check that the hose is secured properly to the unit, and that there is water in the water trap.
Check that the hose is not wrinkled and that there is a minimum gradient of 1% from the unit
to the drain. If the hose is routed to different surrounding temperatures, make sure the hose
is protected against frost damages.
Ensure that the condensate drain is not blocked in the drip tray. Clean the drip tray with
soapy water and a brush or cloth every other year, to ensure good hygiene inside the unit.
Please follow this procedure to clean the drip tray:
Step Action
Illustration
1
Disconnect the 230V AC power supply, and remove the unit cover.
See “Fig. 22” on page 21
2
Remove the drainage hose
and turn all shown locks 90°
3
Gently remove the drip tray.
Please be aware, that if the
unit is underneath the ceil-
ing, it can contain a small
amount of water.
4
Clean and re-insert the drip tray (please check fans according below if needed, prior
to inserting the drip tray)
5
Re-assemble the unit. Check if one water exit is connected, and the opposite drip tray
spigot is blocked.
Drain and hose
(1 year)
Unit driptray
(2 year)