25
Preparations for mounting of the duct air sensor
Bore a Ø9.5 mm hole in the supply air duct (see basic
principle) at a distance of min. 500 mm from the ventilation
unit.
The bigger distance between sensor and unit, the better.
Placing the duct air sensor in a cable relief bushing
Lead the duct air sensor through the relief bushing and
leave a piece of the following length:
Elite 400 approx. 80 mm.
Elite 800 approx. 100 mm.
Placing the duct air sensor in the supply air duct
Tighten the relief bushing around the duct air sensor and
push it into the Ø9.5 mm hole.
Relief bushing
The relief bushing placed in the hole.