13
Description
Value
Off
Temperature when fan stops
20
On
Temperature when Fan starts
23
Min °C
Temperature at bottom of P-band
25
Max °C
Temperature at top of P-band
29
Set Point
The wanted indoor temperature; fan speed will be adjusted between
Min°C and Max °C
27
Emergency on
Fan run 100%
38
Emergency off
Fan go back to nominal speed
36
Free Cooling
Mode
Default Cooling strategies,
continued
Содержание CC 3000
Страница 1: ...Upgrade kit CC3000 controller 28 02 2017 EN Part no 094838...
Страница 11: ...11...
Страница 17: ...17...
Страница 18: ...18...