16
Description
Value
Set Point
External Air Con unit 1 start if connected
27
A/C 1 off
External Air Con unit 1 stops if connected
25
A/C 2 on
External Air Con unit 2 start if connected
29
A/C 2 off
External Air Con unit 2 stops if connected
27
Emergency on
Fan run 100% and both A/C 1 and A/C 2 starts
38
Emergency off
Fan stops both A/C 1 and A/C 2 continue to run
36
Air Conditioner Mode
A/C Status
The free cooling unit is not active, only the connected Air conditioners
Default Cooling strategies,
continued