15
Description
Value
Off
temperature when fan stops
20
On
Temperature when Fan starts
23
Min °C
temperature at bottom of P-band
25
Max °C
Temperature at top of P-band
29
Set Point
The wanted indoor temperature; fan speed will be adjusted
between Min°C and Max °C
27
A/C 1 on
External Air Con unit 1 start if connected
31
A/C 1 off
External Air Con unit 1 stops if connected
29
A/C 2 on
External Air Con unit 2 start if connected
33
A/C 2 off
External Air Con unit 2 stops if connected
31
Emergency on
Fan run 100% and both A/C 1 and A/C 2 starts
38
Emergency off
Fan stops both A/C 1 and A/C 2 continue to run
36
Energy save Mode
(Freecooling > A/C)
If outdoor temperature is less than 1°C colder than indoor room temperature
the Flexibox Fan will stop.
The connected Air-con units will start and stop according to the table above.
Default Cooling strategies,
continued