![Dantherm 3500 Скачать руководство пользователя страница 31](http://html1.mh-extra.com/html/dantherm/3500/3500_installation-manual_3453248031.webp)
31
EN
Technical data
Product overview
Category
DC Split Air Conditioner 3500
DC Air Conditioning
Dantherm No.
364000
Capacity & Performance
Operating range - temperature
°C
-15 to +55
Cooling capacity at 35°C internal and 35°C ambient
W
3624
Cooling capacity at 35°C internal and 25°C ambient
W
3822
Efficiency ratio at 35°C internal and 35°C ambient
COP
3.5
Airflow, maximum internal
m³/h
860
Airflow, maximum external
m³/h
1950
DC supply voltage connection
Type
Flying leads
Input voltage range
VDC
44 to 57
Power consumption (35°C int./35°C ext.)
W
1138
Maximum current, 100%
A
30
Max start current
A
5
Seasonal Energy Efficiency Ratio
SEER
4.5
Max sound level, 1m distance from outdoor unit
dB(A)
57
Expected operation life
Years
10
Dimensions, weight & mounting
Unit dimensions (H X W X D) indoor
mm
286 x 858 x 214
Unit dimensions (H x W x D) outdoor
mm
628 x 785 x 364
Net weight indoor / outdoor
kg
16 / 41
Single package weight incl. unit
kg
75
Single packing dimensions (height × length × depth)
mm
785 x 980 x 640
Storage relative humidity, min./max.
RH %
-5 to +80
Storage temperature, min./max.
°C
-40 to +70
Mounting method
Wall-mounted
Controller details
Controller
Dantherm CC0
Ready for remote
climate control
Communication interface
RS485
Mounting method
Built-in
Certifications
Outdoor unit protection according to EN 60529
IP
55
Indoor unit protection according to EN 60529
IP
21
Refrigerant
R134a / 1100gram
Complies with standards
Code
EN60950 & EN60335-2-40
Colour
RAL
7035
Содержание 3500
Страница 1: ...DC Split Air Conditioner 3500 EN Installation manual Rev 1 0...
Страница 26: ...26 EN Electrical schematic Outdoor Unit Electrical schematic Outdoor unit...
Страница 27: ...27 EN Electrical schematic Indoor Unit Electrical schematic Indoor unit...
Страница 32: ...32 EN Technical data continued Dimensions Outdoor Unit Indoor Unit...
Страница 35: ...35 EN...