Connecting the piping
Find the two insulated rubber hoses and connect the flares to the indoor Unit.
Align the Center of the pipe/hose and tighten the flare nut by hand
And then tighten the flare nut with a wrench
How to connect the
cooling pipes.
9-pin connector
12-pin connector
Grounding
Suction Line 1/2" Flare nut
Drainage
Liquid line 3/8" Flare nut
Flare nut
Tightening
Torque [Nm]
3/8 liquid line
20 to 25
½” suction line 34 to 47
Secure the drainage hose with
the hose clamp.
Installation of indoor, outdoor unit,
continued