VLT is a registered Danfoss trademark
Intro-11
Ratings Table 525-600V / 525-690V
Mains supply 3 x 525-690 V: 5000 & 8000 Series
Mains supply 3 x 525-600 V: 4000 & 6000 Series
Model number
NA*
NA*
NA* VLT 4102 VLT 4122
VLT 5042 VLT 5052 VLT 5062 VLT 5072 VLT 5102
NA*
NA*
NA* VLT 6102 VLT 6122
VLT 8052 VLT 8062 VLT 8072 VLT 8102 VLT 8122
Normal overload current ratings (110 %):
Output current
Nominal [A] (525-550 V)
56
76
90
113
137
MAX (60 sec) [A] (525-550 V)
62
84
99
124
151
Nominal [A] (551-690 V)
54
73
86
108
131
MAX (60 sec) [A] (551-690 V)
59
80
95
119
144
Output
Nominal [kVA] (550 V)
53
72
86
108
131
Nominal [kVA] (575 V)
54
73
86
108
130
Nominal [kVA] (690 V)
65
87
103
129
157
Typical shaft output
[kW] (550 V)
37
45
55
75
90
[HP] (575 V)
50
60
75
100
125
[kW] (690 V)
45
55
75
90
110
High overload torque (160 %):
Output current
Nominal [A] (525-550 V)
48
56
76
90
113
MAX (60 sec) [A] (525-550 V)
77
90
122
135
170
Nominal [A] (551-690 V)
46
54
73
86
108
MAX (60 sec) [A] (551-690 V)
74
86
117
129
162
Output
Nominal [kVA] (550 V)
46
53
72
86
108
Nominal [kVA] (575 V)
46
54
73
86
108
Nominal [kVA] (690 V)
55
65
87
103
129
Typical shaft output
[kW] (550 V)
30
37
45
55
75
[HP] (575 V)
40
50
60
75
100
[kW] (690 V)
37
45
55
75
90
Power loss Normal overload [W]
1458
1717
1913
2262
2662
Power loss High overload [W]
1355
1459
1721
1913
2264
Limits and Ranges
Warning Voltage Low
DC Bus V
585
585
585
585
585
Alarm Voltage Low
DC Bus V
553
553
553
553
553
Warning Voltage High
DC Bus V
1109
1109
1109
1109
1109
Alarm Voltage High
DC Bus V
1130
1130
1130
1130
1130
Brake On Voltage
DC Bus V
1084
1084
1084
1084
1084
Brake On Voltage (Full Duty Cycle)
DC Bus V
1099
1099
1099
1099
1099
SMPS Start Voltage
DC Bus V
508
508
508
508
508
SMPS Stop Voltage
DC Bus V
478
478
478
478
478
Overcurrent Warning
VLT Out
256
256
256
256
256
Overcurrent Alarm (1.5 sec delay)
VLT Out
256
256
256
256
256
Earth Fault Alarm
VLT Out
23
27
37
43
54
Heatsink Over Temperature
Degrees C
75
75
75
75
75
Mains Phase Warning (5 sec delay)
DC Bus Ripple VAC
70
70
70
70
70
Mains Phase Alarm (25 sec delay)
DC Bus Ripple VAC
70
70
70
70
70
Fan On Low Speed Temperature
Degrees C
45
45
45
45
45
Fan On High Sped Temperature
Degrees C
50
50
50
50
50
Fan Off Temperature
Degrees C
<30
<30
<30
<30
<30
Fan Voltage Low Speed
Fan VAC
200
200
200
200
200
Fan Voltage High Speed
Fan VAC
230
230
230
230
230
NA* use existing 525 - 600 V drive
Содержание VLT series
Страница 1: ...MOTION CONTROLS Service Manual VLT 4152 4652 VLT 5122 5602 VLT 6152 6652 VLT 8152 8652...
Страница 8: ......
Страница 20: ......
Страница 32: ......
Страница 41: ...2 9 VLT is a registered Danfoss trademark Figure 2 7 Inverter Section...
Страница 58: ......
Страница 96: ......
Страница 152: ......