VLT is a registered Danfoss trademark
1-5
Table 1-2. VLT 4000/6000/8000 Series Status Definitions
DISPLAY
DESCRIPTION
CONTROL POINT
AUTO
Drive in Auto mode, which means that Run/Stop control is carried out
remotely via input control terminals and/or serial communication.
HAND
Drive in Hand mode, which means that Run/Stop control is carried out
via keys on the keypad.
OFF
OFF/STOP activated either by means of keypad or by digital input
terminals.
REFERENCE LOCATION
REM.
REMOTE selected, which means reference is set via input control
terminals or serial communication.
LOCAL
LOCAL selected, which means reference is set with [+] and [-] keys on
keypad.
DRIVE STATUS
AMA RUN
Automatic motor adaptation enabled in parameter 107,
Automatic Motor
Adaptation, AMA
and drive performing adaptation function.
AMA STOP
Automatic motor adaptation completed. Drive is now ready for
operation after
Reset
enabled. Motor may start after drive reset.
AUTO RAMP
Parameter 208,
Automatic Ramp
, enabled. Drive is attempting to avoid
a trip from overvoltage by extending decel ramp time.
CTR.READY
This status only active when a Profibus option card is installed.
DC STOP
DC brake enabled in parameters 114 through 116.
FRZ.OUT
Drive output frequency frozen at fixed rate from input command.
FRZ.REQ
Start command to run at current frequency given but motor will not start
until a
Run Permission
signal is received via a digital input.
JOG
Jog enabled via digital input or serial communication. Drive is running
at a fixed frequency set in parameter 209,
Jog Frequency.
JOG REQ.
Start command to run at jog frequency given but motor will not start
until a
Run Permission
signal is received via a digital input.
NOT READY
Drive not ready for operation because of a trip or because OFF1, OFF2
or OFF3 is a logic ‘0.’
RAMPING
Motor speed and drive output frequency is changing.
RUN REQ.
Start command given but motor will not start until a
Run Permission
signal is received via digital input.
RUNNING
Motor running and speed corresponds to reference.
SLEEP Parameter
403,
Sleep Mode Timer,
enabled. Motor stopped in sleep
mode. It can restart automatically.
SLEEP.BST
Sleep boost function in parameter 406,
Boost Setpoint,
enabled. Drive
is ramping up to boost setpoint.
STANDBY
Drive able to start motor when a start command is received.
START
Reversing and start
on terminal 19, parameter 303,
Digital Inputs
, and
Start
on terminal 18, parameter 302,
Digital Inputs,
are both enabled.
Motor will remain stopped until either signal becomes logic ‘0.’
START DEL
Start delay time programmed in parameter 111,
Start Delay
. When
delay time expires, drive will start and ramp up to reference frequency.
START IN.
This status only displayed if parameter 599,
Profidrive
[1] selected and
OFF2 or OFF3 is a logic ‘0.’
STOP
Motor stopped via a stop signal from serial communication.
UN.READY
Unit ready for operation but digital input terminal 27 is logic ‘0’ and/or a
Coasting Command
received via serial communication.
XXXX
Control microprocessor stopped for unknown cause and drive not
operating. Cause may be noise on the power line, motor leads or
control wires.
Table 1-2 defines the status line display shown in VLT 4000/
6000/8000 series drives.
Содержание VLT series
Страница 1: ...MOTION CONTROLS Service Manual VLT 4152 4652 VLT 5122 5602 VLT 6152 6652 VLT 8152 8652...
Страница 8: ......
Страница 20: ......
Страница 32: ......
Страница 41: ...2 9 VLT is a registered Danfoss trademark Figure 2 7 Inverter Section...
Страница 58: ......
Страница 96: ......
Страница 152: ......