6-7
VLT is a registered Danfoss trademark
6.9 Soft Charge (SC) Resistors D1 Units
1.
Remove capacitor bank per instruction.
2.
Remove input terminal mounting plate per
instructions.
3.
Note the color coding for each of three wires
attached to terminal 1 for each SCR/Diode
module. Ensure that correct wire is attached to
applicable stud upon reassembling. Remove
wiring from studs. Remove retaining screw (T25)
from terminal 1 of each of 3 SCR/Diode modules
and remove bus bar.
CONTINUED ON NEXT PAGE
Retaining screw
(Step 3)
Bus bar (BB2)
(Step 3)
Soft Charge Resistor
Figure 6-8. D1 Soft Charge Resistor (1 of 3)