
Table 112: 5-15 - Excess Start Time
Range
Function
*20 s 0:00–4:00 (mi-
nutes:seconds)
Excess start time is the maximum time the soft starter attempts to start the motor.
If the motor does not transition to Run mode within the programmed limit, the soft starter trips.
Set for a period slightly longer than required for a normal healthy start. A setting of 0 disables excess
start time protection.
Table 113: 5-16- Restart Delay
Range
Function
*10 s 00:01–60:00 (mi-
nutes:seconds)
The soft starter can be configured to force a delay between the end of a stop and the beginning of
the next start.
During the restart delay period, the display shows the time remaining before another start can be
attempted.
Table 114: 5-17 - Starts per Hour
Range
Function
*0 0–10 Sets the maximum number of starts the soft starter attempts in a 60-minute period. A setting of 0 disables this pro-
tection.
Table 115: 5-18 - Phase Sequence
Option
Function
Selects which phase sequences the soft starter allows at a start. During its pre-start checks, the soft starter
examines the sequence of the phases at its input terminals and trips if the actual sequence does not match
the selected option.
N O T I C E
When using DC brake, the mains supply must be connected to the soft starter (input terminals L1, L2, L3)
in positive phase sequence.
Parameter 5-18 Phase Sequence
must be set to
Positive Only
.
* Any Sequence
Positive only
Negative Only
10.10 Parameter Group 6-** Protection Action
Table 116: 6-1 - Auto-Reset Count
Range
Function
*0
0–5
Sets how many times the soft starter auto-resets if it continues to trip.
The reset counter increases by 1 each time the soft starter auto-resets, and resets after a successful start.
Setting this parameter to 0 disables auto-reset.
Table 117: 6-2 - Auto-Reset Delay
Range
Function
*5 s
0:05–15:00 (minutes:seconds)
Sets a delay before the soft starter auto-resets a trip.
AQ262141844215en-000401 / 175R1174
94 | Danfoss A/S © 2020.12
Programmable Parameters
VLT® Soft Starter MCD 600
Operating Guide
Содержание VLT MCD 600
Страница 1: ...Operating Guide VLT Soft Starter MCD 600 vlt drives danfoss com...
Страница 2: ......
Страница 3: ......
Страница 4: ......
Страница 5: ......
Страница 6: ......
Страница 139: ...AQ262141844215en 000401 175R1174 135 Danfoss A S 2020 12 Index VLT Soft Starter MCD 600 Operating Guide...