Application
Start mode
Start
ramp
time [s]
Initial cur-
rent
(%FLC)
Current
limit
(%FLC)
Stop mode
Stop time
[s]
Pump - submersible
Adaptive control (ear-
ly acceleration)
5
n/a
500
Adaptive control
(late deceleration)
5
Saw - bandsaw
Constant current
1
200
450
Coast to stop
n/a
Saw - circular
Constant current
1
200
350
Coast to stop
n/a
Shredder
Constant current
1
200
450
Coast to stop
n/a
9.8 Soft Start Methods
9.8.1 Constant Current
Constant current is the traditional form of soft starting, which raises the current from 0 to a specified level and keeps the current
stable at that level until the motor has accelerated.
Constant current starting is ideal for applications where the start current must be kept below a particular level.
700
600
500
300
100
400
200
10
20
30
40
50
60
70
80
90
100
e
7
7
h
a
5
0
5
.1
0
1
3
2
%
%
C
u
rr
e
n
t
(%
m
o
to
r
fu
ll
lo
a
d
cu
rr
e
n
t)
Rotor speed (% full speed)
Illustration 29: Example of Constant Current
1
Initial current (set in
parameter 2-3 Initial Current
)
2
Current limit (set in
parameter 2-4 Current Limit
)
3
Full voltage current
9.8.2 Constant Current with Current Ramp
Current ramp soft starting raises the current from a specified starting level (1) to a maximum limit (3) over an extended period (2).
Current ramp starting can be useful for applications where:
The load can vary between starts (for example a conveyor which may start loaded or unloaded). Set
parameter 2-3 Initial Current
to a level that will start the motor with a light load. Then, set
parameter 2-4 Current Limit
to a level that will start the motor with a
heavy load.
The load breaks away easily, but starting time has to be extended (for example a centrifugal pump where pipeline pressure has
to build up slowly).
The electricity supply is limited (for example a generator set), and a slower application of load allows greater time for the supply
to respond.
AQ262141844215en-000401 / 175R1174 | 63
Danfoss A/S © 2020.12
Operation
VLT® Soft Starter MCD 600
Operating Guide