3.0-10:590
3.5-15:585
4.0-10:590
4.0-20:580
5.0-5:595
MCD6-0244B
250
244
230
200
202
MCD6-0287B
352
285
277
234
257
MCD6-0323B
397
322
311
262
288
MCD6-0410B
410
410
410
379
400
MCD6-0527B
550
526
505
427
462
MCD6-0579B
580
578
554
469
507
MCD6-0654B
835
654
630
535
592
MCD6-0736B
940
736
708
603
663
MCD6-0950B
1070
950
905
785
834
MCD6-1154B
1230
1154
1090
959
989
MCD6-1250B
1250
1250
1250
1155
1250
Table 4: In-line Installation, Non-bypassed, MCD6-0160C~MCD6-1134C
3.0-10:50-6
3.5-15:50-6
4.0-10:590
4.0-20:50-6
5.0-5:50-6
MCD6-0160C
190
160
151
144
133
MCD6-0215C
260
215
205
180
192
MCD6-0275C
341
275
266
230
252
MCD6-0343C
404
343
322
296
291
MCD6-0448C
474
448
457
418
470
MCD6-0590C
735
590
572
492
542
MCD6-0667C
830
667
645
557
609
MCD6-0839C
1025
839
805
710
751
MCD6-0979C
1170
979
934
838
862
MCD6-1134C
1220
1134
1109
964
1075
N O T I C E
Models MCD6-0590C~MCD6-1134C must be installed with an external bypass contactor to achieve the bypassed current ratings.
Table 5: In-line Installation, External Bypassed, MCD6-0590C~MCD6-1134C
3.0-10:50-6
3.5-15:50-6
4.0-10:590
4.0-20:50-6
5.0-5:50-6
MCD6-0590C
835
732
716
593
695
MCD6-0667C
940
822
803
667
776
MCD6-0839C
1210
1067
1033
874
982
MCD6-0979C
1430
1307
1252
1076
1170
MCD6-1134C
1620
1620
1616
1309
1620
AQ262141844215en-000401 / 175R1174 | 15
Danfoss A/S © 2020.12
System Design
VLT® Soft Starter MCD 600