MCD6-0160C~MCD6-1134C
IP00
4.7 Heat Dissipation
During start
4.5 W per ampere
During run (bypassed)
MCD6-0020B~MCD6-0042B
≤ 35 W approximately
MCD6-0063B~MCD6-0129B
≤ 50 W approximately
MCD6-0144B~MCD6-0244B
≤ 120 W approximately
MCD6-0287B~MCD6-0579B
≤ 140 W approximately
MCD6-0654B~MCD6-1250B
≤ 180 W approximately
During run (non-bypassed)
MCD6-0160C~MCD6-1134C
4.5 W per ampere
4.8 Motor Overload Protection
The default settings of
parameters 1-4
to
1-6
provide motor over-
load protection.
Class 10, trip current 105% of FLA (full load amperage) or equiva-
lent
4.9 Certification
CCC
GB 14048.6
CE
EN 60947-4-2
UL/C-UL
UL 508
UL
UL 60947-4-2
MCD6-0020B~MCD6-1250B
UL Listed
MCD6-0590C~MCD6-1134C
UL Listed
Marine
Lloyds Marine No 1 specification
All models
ABS: 2010 Steel Vessels Rules
MCD6-0654B~MCD6-1250B & MCD6-0590C~MCD6-1134C
RCM
IEC 60947-4-2
4.10 Operational Life (Internal Bypass Contacts)
Expected operational lifetime
100000 operations
AQ262141844215en-000401 / 175R1174
30 | Danfoss A/S © 2020.12
Specifications
VLT® Soft Starter MCD 600
Operating Guide