Service Code
Supported
Service Name
Description of Service
Class
Instance
0Eh
Yes
Yes
Get_Attribute_Single
returns contents of specified attribute
01h
Yes
Yes
Get_Attributes_All
returns predefined listing of object attributes
10h
No
Yes
Set_Attribute_Single
modifies attribute
4Bh
No
Yes
Get_Enum_String
reads enumerated strings from parameter
instance
Table 8.15 Services supported
Class ID 0x10 Parameter Group Object
Attribute Access
Rule
Name
Data Type
Description
Contents
1
Get
Group Name String
SHORT_STRING
represents group name
Name of Group from
frequency converter
2
Get
Number of group members
UINT
amount of parameters in group
value of n
3
Get
1st group parameter
(000-099)
UINT
instance number of Parameter
Object
variable
4
Get
2nd group parameter
(100-199)
UINT
instance number of Parameter
Object
variable
…
Get
…
UINT
…
variable
n+2
Get
nth group parameter
UINT
instance number of Parameter
Object
variable
Table 8.16 Instance Attributes
Class ID 0x64 – 0xC7 Danfoss Objects
The CIP Class ID 100 to 199 (0x64 to 0xC7) gives access to all parameters.
Class (decimal)
Danfoss Parameter range
100
0-01 - 0-99
101
1-00 – 1-99
102
2-00 – 2-99
103
3-00 – 3-99
104
4-00 – 4-99
105
5-00 – 5-99
106
6-00 – 6-99
107
7-00 – 7-99
108
8-00 – 8-99
109
9-00 – 9-99
110
10-00 – 10-99
111
11-00 – 11-99
…
…
199
99-00 – 99-99
The class Instance and Attribute acts in the following way:
-
100 added to the parameter group = the value
for the class.
-
100 added to the remaining parameter number =
the value for the instance.
-
100 added to the array index of the parameter =
the value for the attribute
Examples: (fictitious parameters)
-
Parameter 0-01 [index 0] = Class 100; Instance
101; Attribute 100
-
Parameter 1-00 [index 0] = Class 101; Instance
100; Attribute 100 - Parameter 2-59[index 0] =
Class 102; Instance 159; Attribute 100
-
Parameter 5-34[index 3] = Class 105; Instance 134;
Attribute 103
-
Parameter 6-54 [index 9] = Class 106; Instance
154; Attribute 109
-
Parameter 10-01 [index 0] = Class 110; Instance
101; Attribute 100
All values in decimal.
All parameters are accessed in the Active setup (
0-10 Active
Set-up
)
Appendix
MCA 121 EtherNet/IP
MG.90.J3.02 - VLT
®
is a registered Danfoss trademark
53
8
8
Содержание VLT MCA 121 EtherNet/IP
Страница 1: ...MAKING MODERN LIVING POSSIBLE Operating Instructions MCA 121 EtherNet IP...
Страница 58: ...www danfoss com drives MG90J302 130R0430 MG90J302 Rev 2011 03 29...
Страница 59: ......