6.2.4 12-3* EtherNet/IP
12-30 Warning parameter
Range:
Function:
[0000 –
FFFF hex]
Read only. Displays the EtherNet/IP specific 16-bit
Status-word.
Bit
Description
0
Owned
1
Not used
2
Configured
3
Not used
4
Not used
5
Not used
6
Not used
7
Not used
8
Minor recoverable fault
9
Minor unrecoverable fault
10
Major recoverable fault
11
Major unrecoverable fault
12
Not used
13
Not used
14
Not used
15
Not used
12-31 Net Reference
Option: Function:
Read only. Displays the reference source in Instance
21/71.
[0]
*
Off Reference from the network is not active.
[1]
On Reference from the network is active.
12-32 Net Control
Option: Function:
Read only. Displays the control source in Instance
21/71.
[0]
*
Off Control via the network is not active.
[1]
On Control via the network is active
12-33 CIP Revision
Option:
Function:
Read only. Displays the CIP-version
of the option software.
[0] Major version (00 - 99)
[1] Minor version (00 - 99)
12-34 CIP Product Code
Range:
Function:
1100 (FC 302) 1110
(FC 301)
*
[0 – 9999] Read only. Displays the CIP
product code.
12-37 COS Inhibit Timer
Range:
Function:
[0 – 65.535
ms]
Read only Change-Of-State inhibit timer. If the
option is configured for COS operation, this
inhibit timer can be configured in the Forward
Open telegram to prevent that continuously
changing PCD data generates extensive network
traffic. The inhibit time is in milliseconds, 0 =
disabled.
12-38 COS Filters
Range:
Function:
[[0 - 9] Filter 0 – 9
(0000 - FFFFhex)]
Change-Of-State PCD filters. Sets up a
filter mask for each word of process
data when operating in COS-mode.
Single bits in the PCD’s can be filtered
in/out.
6.2.5 12-80 Other Ethernet Services
12-80 FTP Server
Option:
Function:
12-81 HTTP Server
Option:
Function:
12-82 SMTP Service
Option:
Function:
12-89 Transent Socket Channel Port
Range:
Function:
0
*
[0 – 9999] Configures the TCP port-number for the transent
socket channel. This enables FC-telegrams to be
sent transently on Ethernet via TCP. Default
value is 4000, 0 means disabled.
12-90 Cable Diagnostic
Option:
Function:
Enables/disables advanced Cable diagnosis
function. If enabled, the distance to cable errors
can be read out in
. The
parameter resumes to the default setting of
Disable after the diagnostics have finished.
[0]
*
Disabled
[1]
Enabled
NOTE
The cable diagnostics function will only be issued on ports
where there is no link (see
12-10 Link Status
,
Link Status
)
12-91 Auto Cross-Over
Option:
Function:
[0]
Disable
Disables the auto cross-over function.
[1]
*
Enable
Enables the auto cross-over function.
Parameters
MCA 121 EtherNet/IP
MG.90.J3.02 - VLT
®
is a registered Danfoss trademark
33
6
6
Содержание VLT MCA 121 EtherNet/IP
Страница 1: ...MAKING MODERN LIVING POSSIBLE Operating Instructions MCA 121 EtherNet IP...
Страница 58: ...www danfoss com drives MG90J302 130R0430 MG90J302 Rev 2011 03 29...
Страница 59: ......