Class ID 0x2A AC/DC Drive Object
Attribute Access Rule
Information about
Data Type
Contents
1
Get
Number of Attributes
Supported
USINT
12
2
Get
List of Attributes Supported
USINT
3,4,6,7,8,18,19,20,21,22,28,29
3
Get
At Reference
Boolean
Bit 8 of FC STW
4
Get/Set
Network Reference
Boolean
value written to parameter "Net Reference"
6
Get/Set
Drive Mode
USINT
Mapping of values from
1-00 Configuration Mode
7
Get
Actual Speed
INT
See Attribute 22
8
Get/Set
Reference Speed
INT
See Attribute 22
18
Get/Set
Acceleration Time
UINT
Scaled with Attribute 28 and written to
3-41 Ramp 1
Ramp up Time
19
Get/Set
Deceleration time
UINT
Scaled with Attribute 28 and written to
3-42 Ramp 1
Ramp Down Time
20
Get/Set
Low Speed Limit
UINT
Scaled with Attribute 22 and written to
4-11 Motor
Speed Low Limit [RPM]
21
Get/Set
High Speed Limit
UINT
Scaled with Attribute 22 and written to
4-13 Motor
Speed High Limit [RPM]
22
Get/Set
Speed Scale
SINT
Forms the "Speed Reference" and "Main Actual Value"
for the frequency converter together with Attribute 7
and 8
28
Get/Set
Time Scale
SINT
Scaling factor for all time attributes
29
Get
Ref From Net
Boolean
value of parameter "Net Reference"
Table 8.8 Instance Attributes
Value of Attribute 6
ODVA Text
Value of
1-00 Configuration Mode
FC Text
0
Vendor specific
Remaining values not listed below
?
1
Open loop speed ctr.
0
Speed open loop
2
Closed loop speed ctr.
1
Speed closed loop
3
Torque Control
NA
NA
4
Process Control
NA
NA
5
Position Control
NA
NA
Table 8.9 Attribute 6 “Drive Mode”
NOTE
Class ID 0x2A is only available if ODVA profile is selected in
.
Appendix
MCA 121 EtherNet/IP
48