5 How to Control
5.1 How to Control
5.1.1 I/O Assembly Instances
I/O Assembly Instances are a number of defined process control objects with defined content comprising control and status
information.
Unlike DeviceNet it is possible to run with asymmetrical instances. E.g. 101/153 = 8 bytes/20 bytes.
It is not possible to mix instances across profiles, e.g. 20/100. Assembly instances must be consistent to the: ODVA or FC
profile.
The controlling instance can be read in par. 12-20,
Control Instance
.
The figure below shows the I/O Assembly Instance options for controlling and monitoring the frequency converter.
Profile
(
Direction
Instances
(decimal)
Size
(bytes)
Data
ODVA
Originator
→
Target
20
4
21
4
Target
→
Originator
70
4
71
4
FC
Originator
→
Target
100
4
101
8
103
20
Target
→
Originator
150
4
151
8
153
20
NOTE
Use of 32-bit process data.
For configuration of a 2-word (32-bit) parameter read/write, use 2 consecutive arrays in par. 12-21 and 12-22, like [2]+[3],
[4]+[5], [6]+[7] etc. Read/write of 2-word values in arrays like: [3]+[4], [5]+[6], [7]+[8] are not possible.
5.1.2 EtherNet/IP Connections
The MCA 121 option supports the CIP connections described in the following sections:
How to Control
MCA 121 EtherNet/IP
MG.90.J3.02 - VLT
®
is a registered Danfoss trademark
17
5
5