![background image](http://html1.mh-extra.com/html/danfoss/vlt-hvac/vlt-hvac_quick-manual_3849138039.webp)
1.7.3 Mains Supply 3 x 380-480 V AC
Frequency
converter
PK75
P1K5
P2K2
P3K0
P4KO
P5K5
P7K5
P11K
P15K
P18K
P22K
P30K
P37K
P45K
P55K
P75K
P90K
Typical
shaft
output
(kW)
0.75
1.5
2.2
3.0
4.0
5.5
7.5
11
15
18.5
22.0
30.0
37.0
45.0
55.0
75.0
90.0
Typical
shaft
output
(hp)
1.0
2.0
3.0
4.0
5.0
7.5
10.0
15.0
20
25.0
30.0
40.0
50.0
60.0
70.0
100.0
125.0
IP54
frame
I2
I2
I2
I2
I2
I3
I3
I5
I5
I5
I6
I6
I6
I7
I7
I8
I8
Max.
cable
size
in
terminals
(mains,
motor)
[mm
2
/AWG]
4/10
4/10
4/10
4/10
4/10
4/10
4/10
10/7
10/7
10/7
35/2
35/2
35/2
50/1
50/1
95/
(3/0)
120/
(4/0)
Output
current
40
°
C
ambient
temperature
Continuous
(3
x
380-440
V)
[A]
2.2
3.7
5.3
7.2
9.0
12.0
15.5
24
32
37.5
44.0
61.0
73.0
90.0
106.0
147.0
177.0
Intermittent
(3
x
380-440
V)
[A]
2.4
4.1
5.8
7.9
9.9
13.2
17.1
26.2
35.2
41.3
48.4
67.1
80.3
99.0
116.6
161.7
194.7
Continuous
(3
x
440-480
V)
[A]
2.1
3.4
4.8
6.3
8.2
11.0
14.0
21
27
34
40.0
52.0
65.0
80.0
105.0
130.0
160.0
Intermittent
(3
x
440-480
V)
[A]
2.3
3.7
5.3
6.9
9.0
12.1
15.4
23.1
29.7
37.4
44.0
57.2
71.5
88.0
115.5
143.0
176.0
Max.
input
current
Continuous
(3
x
380-440
V
)[A]
2.1
3.5
4.7
6.3
8.3
11.2
15.1
22
29
34
41.8
57.0
70.3
84.2
102.9
140.3
165.6
Intermittent
(3
x
380-440
V)
[A]
2.3
3.9
5.2
6.9
9.1
12.3
16.6
24.2
31.9
37.3
46.0
62.7
77.4
92.6
113.1
154.3
182.2
Continuous
(3
x
440-480
V)
[A]
1.8
2.9
3.9
5.3
6.8
9.4
12.6
19
25
31
36.0
49.2
60.6
72.5
88.6
120.9
142.7
Intermittent
(3
x
440-480
V)
[A]
2.0
3.2
4.3
5.8
7.5
10.3
13.9
20.9
27.5
34.1
39.6
54.1
66.7
79.8
97.5
132.9
157.0
Max.
mains
fuses
Quick Guide
VLT HVAC Basic Drive Quick Guide
38
MG18A302 - VLT
®
is a registered Danfoss trademark
1