1.5 Parameter Overview
Parameter Overview
0-** Operation / Display
0-0* Basic Settings
0-01 Language
*[0] English
[1] Deutsch
[2] Francais
[3] Dansk
[4] Espanol
[5] Italiano
[28] Portuguese
[255] No Text
0-03 Regional Settings
*[0] International
[1] US
0-04 Operating State at Power-
up
*[0] Resume
[1] Forced stop, ref=old
0-06 GridType
0] 200-240 V/50 Hz/IT-grid
[1] 200-240 V/50 Hz/Delta
[2] 200-240 V/50 Hz
[10] 380-440 V/50 Hz/IT-grid
[11] 380-440 V/50 Hz/Delta
[12] 380-440 V/50 Hz
[20] 440-480 V/50 Hz/IT-grid
[21] 440-480 V/50 Hz/Delta
[22] 440-480 V/50 Hz
[30] 525-600 V/50 Hz/IT-grid
[31] 525-600 V/50 Hz/Delta
[32] 525-600 V/50 Hz
[100] 200-240 V/60 Hz/IT-grid
[101] 200-240 V/60 Hz/Delta
[102] 200-240 V/60 Hz
[110] 380-440 V/60 Hz/IT-grid
[111] 380-440 V/60 Hz/Delta
[112] 380-440 V/60 Hz
[120] 440-480 V/60 Hz/IT-grid
[121] 440-480 V/60 Hz/Delta
[122] 440-480 V/60 Hz
[130] 525-600 V/60 Hz/IT-grid
[131] 525-600 V/60 Hz/Delta
[132] 525-600 V/60 Hz
0-07 Auto DC Braking IT
[0] Off
*[1] On
0-1* Set-up Operations
0-10 Active Set-up
*[1] Set-up 1
[2] Set-up 2
[9] Multi Set-up
0-11 Programming Set-up
[1] Set-up 1
[2] Set-up 2
*[9] Active Set-up
0-12 Link Setups
[0] Not linked
*[20] Linked
0-3* LCP Readout
0-30 Custom Readout Unit
[0] None
*[1] %
[5] PPM
[10] 1/Min
[11] RPM
[12] Pulse/s
[20] l/s
[21] l/min
[22] l/h
[23] m3/s
[24] m3/min
[25] m3/h
[30] kg/s
[31] kg/min
[32] kg/h
[33] t/min
[34] t/h
[40] m/s
[41] m/min
[45] m
[60] Degree Celsius
[70] mbar
[71] bar
[72] Pa
[73] kPa
[74] m Wg
[80] kW
[120] GPM
[121] gal/s
[122] gal/min
[123] gal/h
[124] CFM
[127] ft3/h
[140] ft/s
[141] ft/min
[160] Degree Fahr
[170] psi
[171] lb/in2
[172] in WG
[173] ft WG
[180] HP
0-31 Custom Readout Min Value
0.00 - 1,000,000.0, * 0.00
0-32 Custom Readout Max Value
0.00 - 1,000,000.0, * 100.00
0-37 Display Text 1
0-38 Display Text 2
0-39 Display Text 3
0-4* LCP Keypad
0-40 [Hand on] Key on LCP
[0] Disabled
*[1] Enabled
0-42 [Auto on] Key on LCP
[0] Disabled
*[1] Enabled
0-44 [Off / Reset] Key on LCP
[0] Disable All
*[1] Enable All
[7] Enable Reset Only
0-5* Copy/Save
0-50 LCP Copy
*[0] No copy
[1] All to LCP
[2] All from LCP
[3] Size indep. from LCP
0-51 Set-up Copy
*[0] No copy
[1] Copy from setup 1
[2] Copy from setup 2
[9] Copy from Factory setup
0-6* Password
0-60 Main Menu Password
0 - 999, * 0
1-** Load and Motor
1-0* General Settings
1-00 Configuration Mode
*[0] Open loop
[3] Closed loop
1-01 Motor Control Principle
[0] U/f
*[1] VVC+
1-03 Torque Characteristics
*[1] Variable torque
[3] Auto Energy Optim.
1-06 Clockwise Direction
*[0] Normal
[1] Inverse
1-20 Motor Power
[2] 0.12 kW - 0.16 Hp
[3] 0.18 kW - 0.25 Hp
[4] 0.25 kW - 0.33 Hp
[5] 0.37 kW - 0.50 Hp
[6] 0.55 kW - 0.75 Hp
[7] 0.75 kW - 1.00 Hp
[8] 1.10 kW - 1.50 Hp
[9] 1.50 kW - 2.00 Hp
[10] 2.20 kW - 3.00 Hp
[11] 3.00 kW - 4.00 Hp
[12] 3.70 kW - 5.00 Hp
[13] 4.00 kW - 5.40 Hp
[14] 5.50 kW - 7.50 Hp
[15] 7.50 kW - 10.0 Hp
[16] 11.00 kW - 15.00 Hp
[17] 15.00 kW - 20 Hp
[18] 18.5 kW - 25 Hp
[19] 22 kW - 30 Hp
[20] 30 kW - 40 Hp
[21] 37 kW-50 Hp
[22] 45 kW-60 Hp
[23] 55 kW-75 Hp
[24] 75 kW-100 Hp
[25] 90 kW-120 Hp
[26] 110 kW-150 Hp
1-22 Motor Voltage
50 - 1000 V
1-23 Motor Frequency
20 - 400, *(50) Hz
1-24 Motor Current
0.01 - (26.00), [A]
1-25 Motor Nominal Speed
100 rpm - 6000 rpm,
1-29 Automatic Motor Adaption
(AMA)
*[0] Off
[1] Enable Complete AMA
[2] Enable Reduced AMA
1-3* Adv. Motor Data I
1-30 Stator Resistance (Rs)
0.000 ohm - 99.990 ohm
1-33 Stator Leakage Reactance
(X1)
0.000 ohm - 999.900 ohm
1-35 Main Reactance (Xh)
0.00 - 999.90 ohm
1-39 Motor Poles
2 - 100, * 4
1-4* Adv. Motor Data II
1-42 Motor Cable Length
0 - 150, * 50m
1-43 Motor Cable Length Feet
0 - 431, * 144
1-5* Load Indep. Setting
1-50 Motor Magnetisation at
Zero Speed
0 - 300, * 100%
1-52 Min Speed Normal
Magnetising [Hz]
0.0 - 10.0, * 0.0
1-55 U/f Characteristic - U
0 - 999 V, *0V
1-56 U/f Characteristic - F
0 - 400 Hz, *(0)
1-6* Load Depend. Setting
1-62 Slip Compensation
-400 - 399%, * 0%
Quick Guide
VLT HVAC Basic Drive Quick Guide
28
MG18A302 - VLT
®
is a registered Danfoss trademark