The FC101 Start-up Wizard for Open Loop Applications
No & Name
Range
Default
Function
0-03 Regional Settings
[0] International
[1] US
0
0-06 Grid Type
[0] 200-240 V/50 Hz/IT-grid
[1] 200-240 V/50 Hz/Delta
[2] 200-240 V/50 Hz
[10] 380-440 V/50 Hz/IT-grid
[11] 380-440 V/50 Hz/Delta
[12] 380-440 V/50 Hz
[20] 440-480 V/50 Hz/IT-grid
[21] 440-480 V/50 Hz/Delta
[22] 440-480 V/50 Hz
[30] 525-600 V/50 Hz/IT-grid
[31] 525-600 V/50 Hz/Delta
[32] 525-600 V/50 Hz
[100] 200-240 V/60 Hz/IT-grid
[101] 200-240 V/60 Hz/Delta
[102] 200-240 V/60 Hz
[110] 380-440 V/60 Hz/IT-grid
[111] 380-440 V/60 Hz/Delta
[112] 380-440 V/60 Hz
[120] 440-480 V/60 Hz/IT-grid
[121] 440-480 V/60 Hz/Delta
[122] 440-480 V/60 Hz
[130] 525-600 V/60 Hz/IT-grid
[131] 525-600 V/60 Hz/Delta
[132] 525-600 V/60 Hz
Size related
Select operating mode for restart upon
reconnection of the drive to mains voltage after
power down
1-20 Motor Power
0.12-110 kW/0.16-150 hp
Size related
Enter motor power from nameplate data
1-22 Motor Voltage
50.0 - 1000.0 V
Size related
Enter motor voltage from nameplate data
1-23 Motor Frequency
20.0 - 400.0 Hz
Size related
Enter motor frequency from nameplate data
1-24 Motor Current
0.01 - 10000.00 A
Size related
Enter motor current from nameplate data
1-25 Motor Nominal
Speed
100.0 - 9999.0 RPM
Size related
Enter motor nominal speed from nameplate data
4-12 Motor Speed Low
Limit [Hz]
0.0 - 400 Hz
0 Hz
Enter the minimum limit for low speed
4-14 Motor Speed High
Limit [Hz]
0.0 - 400 Hz
65 Hz
Enter the maximum limit for high speed
3-41 Ramp 1 Ramp up
Time
0.05 - 3600.0 s
Size related
Ramp up time from 0 to rated
1-23 Motor
Frequency
3-42 Ramp 1 Ramp
Down Time
0.05 - 3600.0 s
Size related
Ramp down time from rated
1-23 Motor Frequency
to 0
1-73 Flying Start
[0] Disabled
[1] Enabled
0
Select Enable to enable the frequency converter to
catch a spinning motor i.e. fan applications
6-19 Terminal 53 mode
[0] Current
[1] Voltage
1
Select if terminal 53 is used for current- or voltage
input
6-10 Terminal 53 Low
Voltage
0-10 V
0.07 V
Enter the voltage that corresponds to the low
reference value
6-11 Terminal 53 High
Voltage
0-10 V
10 V
Enter the voltage that corresponds to the high
reference value
6-12 Terminal 53 Low
Current
0-20 mA
4
Enter the current that corresponds to the low
reference value
6-13 Terminal 53 High
Current
0-20 mA
20
Enter the current that corresponds to the high
reference value
3-02 Minimum Reference -4999-4999
0
The minimum reference is the lowest value
obtainable by summing all references
Quick Guide
VLT HVAC Basic Drive Quick Guide
MG18A302 - VLT
®
is a registered Danfoss trademark
23