2-17
Overvoltage Control
Value:
Disabled
[0]
Enabled
[2]
Function:
Overvoltage control (OVC) reduces the risk of
the adjustable frequency drive tripping due to
an overvoltage in the DC link caused by gen-
erative power from the load.
Select
Disabled
[0] if no OVC is required.
Select
Enabled
[2] to activate OVC.
NOTE
The ramp time is automatically
adjusted to prevent the adjust-
able frequency drive from trip-
ping.
3-02
Minimum Reference
Value:
-100,000.000 – par. 3-03
0.000 Unit
Function:
Enter the Minimum Reference. The Minimum
Reference is the lowest value obtainable by
adding all references together.
3-03
Maximum Reference
Value:
Par. 3-02 - 100000.000
0.000 Unit
Function:
Enter the maximum reference. The maximum
reference is the highest value obtainable by
adding all references together.
3-10
Preset Reference
Array [8]
Value:
-100.00% - +100.00%
0.00%
Function:
Enter up to eight different preset references
(0-7) in this parameter using array program-
ming. The preset reference is stated as a per-
centage of the value Ref
MAX
(par. 3-03
Maximum Reference
) or as a percentage of
the other external references. If a Ref
MIN
dif-
ferent from 0 (Par. 3-02
Minimum Reference
)
is programmed, the preset reference is calcu-
lated as a percentage of the full reference
range, i.e., on the basis of the difference be-
tween Ref
MAX
and Ref
MIN
. Afterwards, the val-
ue is added to Ref
MIN
. When using preset
references, select Preset ref. bit 0 / 1 / 2 [16],
[17] or [18] for the corresponding digital in-
puts in parameter group 5.1* Digital Inputs.
3-15
Reference 1 Source
Value:
No function
[0]
Analog input 53
[1]
Analog input 54
[2]
Frequency input 29
[7]
Frequency input 33
[8]
Digital pot. meter
[20]
Analog input X30-11
[21]
Analog input X30-12
[22]
Analog Input X42/1
[23]
Analog Input X42/3
[24]
Analog Input X42/5
[25]
Ext. Closed-loop 1
[30]
Ext. Closed-loop 2
[31]
Ext. Closed-loop 3
[32]
6. How to program the adjustable frequency
drive
VLT
®
HVAC Drive Instruction Manual
82
MG.11.A4.22
-
VLT
®
is a registered Danfoss trademark
6