Protection and Features:
•
Electronic thermal motor protection against overload.
•
Temperature monitoring of the heatsink ensures that the adjustable frequency drive trips
if the temperature reaches 203°F ± 9°F [95 °C ± 5°C]. An overload temperature cannot
be reset until the temperature of the heatsink is below 158°C ± 9°C [70°C ± 5°C]
(Guideline - these temperatures may vary for different power sizes, enclosures, etc.).
VLT HVAC drive has an auto-derating function to prevent it's heatsink from reaching 203°
F [95°C].
•
The adjustable frequency drive is protected against short-circuits on motor terminals U,
V, W.
•
If a line phase is missing, the adjustable frequency drive trips or issues a warning (de-
pending on the load).
•
Monitoring of the intermediate circuit voltage ensures that the adjustable frequency drive
trips if the intermediate circuit voltage is too low or too high.
•
The adjustable frequency drive is protected against ground faults on motor terminals U,
V, W.
Line power supply (L1, L2, L3):
Supply voltage
200-240 V ±10%
Supply voltage
380-480 V ±10%
Supply voltage
525-600 V ±10%
Supply frequency
50/60 Hz
Max. imbalance temporary between line phases
3.0% of rated supply voltage
True Power Factor (
λ
)
≥
0.9 nominal at rated load
Displacement Power Factor (cos
φ
) near unity
(> 0.98)
Switching on input supply L1, L2, L3 (power-ups)
≤
enclosure type A
maximum twice/min.
Switching on input supply L1, L2, L3 (power-ups)
≥
enclosure type B, C
maximum once/min.
Environment according to EN60664-1
overvoltage category III/pollution degree 2
The unit is suitable for use on a circuit capable of delivering no more than 100,000 RMS sym-
metrical Amperes, 240/500/600 V maximum.
Motor output (U, V, W):
Output voltage
0 - 100% of supply voltage
Output frequency
0 - 1000 Hz
Switching on output
Unlimited
Ramp times
1 - 3600 sec.
Torque characteristics:
Starting torque (Constant torque)
maximum 110% for 1 min.
*
Starting torque
maximum 120% up to 0.5 sec.
*
Overload torque (Constant torque)
maximum 110% for 1 min.
*
*Percentage relates to the nominal torque for the VLT HVAC Drive.
8. Specifications
VLT
®
HVAC Drive Instruction Manual
144
MG.11.A4.22 - VLT
®
is a registered Danfoss trademark
8