Pulse inputs:
Programmable pulse inputs
2
Terminal number pulse
29, 33
Max. frequency at terminal, 29, 33
110 kHz (push-pull driven)
Max. frequency at terminal, 29, 33
5 kHz (open collector)
Min. frequency at terminal 29, 33
4 Hz
Voltage level
see section on Digital input
Maximum voltage on input
28 V DC
Input resistance, R
i
approx. 4 k
Ω
Pulse input accuracy (0.1-1 kHz)
Max. error: 0.1% of full scale
Analog output:
Number of programmable analog outputs
1
Terminal number
42
Current range at analog output
0/4 - 20 mA
Max. load to common at analog output
500
Ω
Accuracy on analog output
Max. error: 0.8% of full scale
Resolution on analog output
8 bit
The analog output is galvanically isolated from the supply voltage (PELV) and other high-voltage
terminals.
Control card, RS-485 serial communication:
Terminal number
68 (P,TX+, RX+), 69 (N,TX-, RX-)
Terminal number 61
Common for terminals 68 and 69
The RS-485 serial communication circuit is functionally separated from other central circuits and
galvanically isolated from the supply voltage (PELV).
8. Specifications
VLT
®
HVAC Drive Instruction Manual
146
MG.11.A4.22 - VLT
®
is a registered Danfoss trademark
8