Control card, 10 V DC output:
Terminal number
50
Output voltage
10.5 V ±0.5 V
Max. load
25 mA
The 10 V DC supply is galvanically isolated from the supply voltage (PELV) and other high-voltage
terminals.
Control characteristics:
Resolution of output frequency at 0 - 1000 Hz
: +/- 0.003 Hz
System response time (terminals 18, 19, 27, 29, 32, 33)
:
≤
2 ms
Speed control range (open-loop)
1:100 of synchronous speed
Speed accuracy (open-loop)
30 - 4000 rpm: Maximum error of ±8 rpm
All control characteristics are based on a 4-pole asynchronous motor
Surroundings:
Enclosure
≤
enclosure type A
IP 20, IP 55
Enclosure
≥
enclosure type A, B
IP 21, IP 55
Enclosure kit available
≤
enclosure type A
IP 21/TYPE 1/IP 4X top
Vibration test
1.0 g
Max. relative humidity
5% - 95% (IEC 721-3-3); Class 3K3 (non-condensing) during operation
Aggressive environment (IEC 721-3-3), uncoated
class 3C2
Aggressive environment (IEC 721-3-3), coated
class 3C3
Test method according to IEC 60068-2-43 H2S (10 days)
Ambient temperature
Max. 122°F [50°C]
Derating for high ambient temperature, see section on special conditions
Minimum ambient temperature during full-scale operation
32°F [0°C]
Minimum ambient temperature at reduced performance
14°F [-10°C]
Temperature during storage/transport
-13° - +149/158°F [-25° - +65/70°C]
Maximum altitude above sea level without derating
3281 ft. [1000 m]
Maximum altitude above sea level with derating
9842 ft [3000 m]
Derating for high altitude, see section on special conditions.
EMC standards, Emission
EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3
EMC standards, Immunity
EN 61800-3, EN 61000-6-1/2,
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN
61000-4-6
See section on special conditions
Control card performance:
Scan interval
: 5 ms
Control card, USB serial communication:
USB standard
1.1 (Full speed)
USB plug
USB type B “ device” plug
Connection to PC is carried out via a standard host/device USB cable.
The USB connection is galvanically isolated from the supply voltage (PELV) and other high-volt-
age terminals.
The USB connection is not galvanically isolated from protection ground. Use only an isolated
laptop as a PC connection to the USB connector on the VLT HVAC Drive.
8. Specifications
VLT
®
HVAC Drive Instruction Manual
148
MG.11.A4.22 - VLT
®
is a registered Danfoss trademark
8
Содержание VLT HVAC
Страница 10: ...2 Introduction VLT HVAC Drive Instruction Manual 10 MG 11 A4 22 VLT is a registered Danfoss trademark 2...
Страница 130: ...7 Troubleshooting VLT HVAC Drive Instruction Manual 130 MG 11 A4 22 VLT is a registered Danfoss trademark 7...
Страница 138: ...8 Specifications VLT HVAC Drive Instruction Manual 138 MG 11 A4 22 VLT is a registered Danfoss trademark 8...