Input
Digital/analog
Supply Voltage
Volt
Threshold
Cut-out Values
Digital
24 V
< 6.6 k
Ω
- > 10.8 k
Ω
Digital
10 V
< 800
Ω
- > 2.7 k
Ω
Analog
10 V
< 3.0 k
Ω
- > 3.0 k
Ω
NOTE
Check that the chosen supply voltage follows the
specification of the used thermistor element.
[3]
ETR warning 1
ETR Warning 1-4
, activate a warning on the display when the
motor is overloaded.
[4]
*
ETR trip 1
ETR Trip 1-4
trip the frequency converter when the motor is
overloaded.
Programme a warning signal via one of the digital outputs. The
signal appears in the event of a warning and if the frequency
converter trips (thermal warning).
[5]
ETR warning 2
See [3]
[6]
ETR trip 2
See [4]
[7]
ETR warning 3
See [3]
[8]
ETR trip 3
See [4]
[9]
ETR warning 4
See [3]
[10]
ETR trip 4
See [4]
ETR (Electronic Thermal Relay) functions 1-4 will calculate the load when the set-up where they
were selected is active. For example ETR starts calculating when setup 3 is selected. For the North
American market: The ETR functions provide class 20 motor overload protection in accordance
with NEC.
6. How to program the adjustable frequency
drive
VLT
®
HVAC Drive Instruction Manual
80
MG.11.A4.22
-
VLT
®
is a registered Danfoss trademark
6
Содержание VLT HVAC
Страница 10: ...2 Introduction VLT HVAC Drive Instruction Manual 10 MG 11 A4 22 VLT is a registered Danfoss trademark 2...
Страница 130: ...7 Troubleshooting VLT HVAC Drive Instruction Manual 130 MG 11 A4 22 VLT is a registered Danfoss trademark 7...
Страница 138: ...8 Specifications VLT HVAC Drive Instruction Manual 138 MG 11 A4 22 VLT is a registered Danfoss trademark 8...