Programmable relay outputs
Relay 01 terminal number (enclosure size H9)
01–03 (NC), 01–02 (NO)
Maximum terminal load (AC-1)
(1)
on 01–03 (NC), 01–02 (NO) (resistive load)
240 V AC, 2 A
Maximum terminal load (AC-15)
(1)
(inductive load @ cosφ 0.4)
240 V AC, 0.2 A
Maximum terminal load (DC-1)
(1)
on 01–02 (NO), 01–03 (NC) (resistive load)
60 V DC, 1 A
Maximum terminal load (DC-13)
(1)
(inductive load)
24 V DC, 0.1 A
Relay 01 and 02 terminal number (enclosure size H6, H7, H8, H9 (relay 2 only), H10, and
I6–I8)
01–03 (NC), 01–02 (NO), 04–06 (NC), 04– 05
(NO)
Maximum terminal load (AC-1)
(1)
on 04–05 (NO) (resistive load)
(2) (3)
400 V AC, 2 A
Maximum terminal load (AC-15)
(1)
on 04–05 (NO) (inductive load @ cosφ 0.4)
240 V AC, 0.2 A
Maximum terminal load (DC-1)
(1)
on 04–05 (NO) (resistive load)
80 V DC, 2 A
Maximum terminal load (DC-13)
(1)
on 04–05 (NO) (inductive load)
24 V DC, 0.1 A
Maximum terminal load (AC-1)
(1)
on 04–06 (NC) (resistive load)
240 V AC, 2 A
Maximum terminal load (AC-15)
(1)
on 04–06 (NC) (inductive load @ cosφ 0.4)
240 V AC, 0.2 A
Maximum terminal load (DC-1)
(1)
on 04–06 (NC) (resistive load)
50 V DC, 2 A
Maximum terminal load (DC-13)
(1)
on 04–06 (NC) (inductive load)
24 V DC, 0.1 A
Minimum terminal load on 01–03 (NC), 01–02 (NO), 04–06 (NC), 04–05 (NO)
24 V DC 10 mA, 24 V AC 20 mA
Environment according to EN 60664-1
Overvoltage category III/pollution degree 2
1
IEC 60947 parts 4 and 5. Endurance of the relay varies with different load type, switching current, ambient temperature, driving configuration, working profile, and so forth. It is
recommended to mount a snubber circuit when connecting inductive loads to the relays.
2
Overvoltage Category II.
3
UL applications 300 V AC 2 A.
6.4.12 Control Card, 10 V DC Output
Terminal number
50
Output voltage
10.5 V ±0.5 V
Maximum load
25 mA
6.4.13 Ambient Conditions
Enclosure protection rating
IP20, IP54 (not for outdoor installation)
Enclosure kit available
IP21, TYPE 1
Vibration test
1.0 g
Maximum relative humidity
5–95% (IEC 60721-3-3; Class 3K3 (non-condensing)) during
operation
Aggressive environment (IEC 60721-3-3), coated (standard) enclosure
sizes H1–H5
Class 3C3
Aggressive environment (IEC 60721-3-3), non-coated enclosure sizes
H6–H10
Class 3C2
Aggressive environment (IEC 60721-3-3), coated (optional) enclosure
sizes H6–H10
Class 3C3
Specifications
Operating Guide | VLT® HVAC Basic Drive FC 101
AQ275641848264en-000101 / 132R0078
78 | Danfoss A/S © 2019.11