Drive
P22K
P30K
P37K
P45K
P55K
P75K
P90K
Continuous (3x380–440 V) [A]
35.2
48.8
58.4
63.0
74.2
102.9
123.9
Intermittent (3x380–440 V) [A]
38.7
53.9
64.2
69.3
81.6
113.2
136.3
Continuous (3x441–480 V) [A]
32.0
41.6
52.0
56.0
73.5
91.0
112.0
Intermittent (3x441–480 V) [A]
35.2
45.8
57.2
61.6
80.9
100.1
123.2
1
Applies for dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and typical control card power consump-
tions are included. For power loss data according to EN 50598-2, refer to Danfoss
website.
2
Efficiency measured at nominal current. For energy efficiency class, see
. For part load losses, see Danfoss
website.
6.1.3 3x525–600 V AC
Table 26: 3x525–600 V AC, 2.2–15 kW (3–20 hp), Enclosure Sizes H9–H10
Drive
P2K2
P3K0
P3K7
P5K5
P7K5
P11K
P15K
Typical shaft output [kW]
2.2
3.0
3.7
5.5
7.5
11.0
15.0
Typical shaft output [hp]
3.0
4.0
5.0
7.5
10.0
15.0
20.0
Protection rating IP20
H9
H9
H9
H9
H9
H10
H10
Maximum cable size in terminals
(mains, motor) [mm
2
(AWG)]
4 (10)
4 (10)
4 (10)
4 (10)
4 (10)
10 (8)
10 (8)
Output current - 40°C (104°F) ambient temperature
Continuous (3x525–550 V) [A]
4.1
5.2
6.4
9.5
11.5
19.0
23.0
Intermittent (3x525–550 V) [A]
4.5
5.7
7.0
10.5
12.7
20.9
25.3
Continuous (3x551–600 V) [A]
3.9
4.9
6.1
9.0
11.0
18.0
22.0
Intermittent (3x551–600 V) [A]
4.3
5.4
6.7
9.9
12.1
19.8
24.2
Maximum input current
Continuous (3x525–550 V) [A]
3.7
5.1
5.0
8.7
11.9
16.5
22.5
Intermittent (3x525–550 V) [A]
4.1
5.6
6.5
9.6
13.1
18.2
24.8
Continuous (3x551–600 V) [A]
3.5
4.8
5.6
8.3
11.4
15.7
21.4
Intermittent (3x551–600 V) [A]
3.9
5.3
6.2
9.2
12.5
17.3
23.6
Maximum mains fuses
See
3.2.4.5 Recommendation of Fuses and Circuit Breakers
Estimated power loss [W], best
case/typical
(1)
65
90
110
132
180
216
294
Weight enclosure protection rat-
ing IP54 [kg (lb)]
6.6 (14.6)
6.6 (14.6)
6.6 (14.6)
6.6 (14.6)
6.6 (14.6)
11.5 (25.3)
11.5 (25.3)
Efficiency [%], best case/typical
(2)
97.9
97
97.9
98.1
98.1
98.4
98.4
Output current - 50°C (122°F) ambient temperature
Continuous (3x525–550 V) [A]
2.9
3.6
4.5
6.7
8.1
13.3
16.1
Intermittent (3x525–550 V) [A]
3.2
4.0
4.9
7.4
8.9
14.6
17.7
Specifications
Operating Guide | VLT® HVAC Basic Drive FC 101
AQ275641848264en-000101 / 132R0078| 71
Danfoss A/S © 2019.11
Содержание VLT HVAC Basic Drive FC 101
Страница 1: ...Operating Guide VLT HVAC Basic Drive FC 101...
Страница 2: ......
Страница 82: ...Operating Guide VLT HVAC Basic Drive FC 101 AQ275641848264en 000101 132R0078 82 Danfoss A S 2019 11...
Страница 83: ...Operating Guide VLT HVAC Basic Drive FC 101 AQ275641848264en 000101 132R0078 83 Danfoss A S 2019 11...