3 Installation
3.1 Mechanical Installation
3.1.1 Side-by-side Installation
The drive can be mounted side-by-side but requires the clearance above and below for cooling.
Table 5: Clearance Required for Cooling
Power [kW (hp)]
Clearance above/below [mm (in)]
Size
IP class
3x200–240 V
3x380–480 V
3x525–600 V
H1
IP20
0.25–1.5 (0.33–2)
0.37–1.5 (0.5–2)
–
100 (4)
H2
IP20
2.2 (3)
2.2–4 (3–5)
–
100 (4)
H3
IP20
3.7 (5)
5.5–7.5 (7.5–10)
–
100 (4)
H4
IP20
5.5–7.5 (7.5–10)
11–15 (15–20)
–
100 (4)
H5
IP20
11 (15)
18.5–22 (25–30)
–
100 (4)
H6
IP20
15–18.5 (20–25)
30–45 (40–60)
18.5–30 (25–40)
200 (7.9)
H7
IP20
22–30 (30–40)
55–75 (70–100)
37–55 (50–70)
200 (7.9)
H8
IP20
37–45 (50–60)
90 (125)
75–90 (100–125)
225 (8.9)
H9
IP20
–
–
2.2–7.5 (3–10)
100 (4)
H10
IP20
–
–
11–15 (15–20)
200 (7.9)
I2
IP54
–
0.75–4.0 (1–5)
–
100 (4)
I3
IP54
–
5.5–7.5 (7.5–10)
–
100 (4)
I4
IP54
–
11–18.5 (15–25)
–
100 (4)
I6
IP54
–
22–37 (30–50)
–
200 (7.9)
I7
IP54
–
45–55 (60–70)
–
200 (7.9)
I8
IP54
–
75–90 (100–125)
–
225 (8.9)
NOTICE
With IP21/NEMA Type1 option kit mounted, a distance of 50 mm (2 in) between the units is required.
Installation
Operating Guide | VLT® HVAC Basic Drive FC 101
AQ275641848264en-000101 / 132R0078
12 | Danfoss A/S © 2019.11