6.4 General Technical Data
6.4.1 Protection and Features
•
Electronic motor thermal protection against overload.
•
Temperature monitoring of the heat sink ensures that the drive trips if there is overtemperature.
•
The drive is protected against short circuits between motor terminals U, V, W.
•
When a motor phase is missing, the drive trips and issues an alarm.
•
When a mains phase is missing, the drive trips or issues a warning (depending on the load).
•
Monitoring of the DC-link voltage ensures that the drive trips when the DC-link voltage is too low or too high.
•
The drive is protected against ground faults on motor terminals U, V, W.
6.4.2 Mains Supply (L1, L2, L3)
Supply voltage
200–240 V ±10%
Supply voltage
380–480 V ±10%
Supply voltage
525–600 V ±10%
Supply frequency
50/60 Hz
Maximum imbalance temporary between mains phases
3.0% of rated supply voltage
True power factor (λ)
≥0.9 nominal at rated load
Displacement power factor (cosφ) near unity
(>0.98)
Switching on the input supply L1, L2, L3 (power-ups) enclosure sizes H1–H5, I2, I3, I4
Maximum 1 time/30 s
Switching on the input supply L1, L2, L3 (power-ups) enclosure sizes H6–H10, I6–I8
Maximum 1 time/minute
Environment according to EN 60664-1
Overvoltage category III/pollution degree 2
The unit is suitable for use on a circuit capable of delivering not more than 100000 A
rms
symmetrical Amperes, 240/480 V maximum.
6.4.3 Motor Output (U, V, W)
Output voltage
0–100% of supply voltage
Output frequency
0–400 Hz
Switching on output
Unlimited
Ramp times
0.05–3600 s
6.4.4 Cable Length and Cross-section
Maximum motor cable length, shielded/armored (EMC-correct installation)
See
.
Maximum motor cable length, unshielded/unarmoured
50 m (164 ft)
Maximum cross-section to motor, mains
See
Cross-section DC terminals for filter feedback on enclosure sizes H1–H3, I2, I3, I4
4 mm
2
/11 AWG
Cross-section DC terminals for filter feedback on enclosure sizes H4–H5
16 mm
2
/6 AWG
Maximum cross-section to control terminals, rigid wire
2.5 mm
2
/14 AWG
Maximum cross-section to control terminals, flexible cable
2.5 mm
2
/14 AWG
Specifications
Operating Guide | VLT® HVAC Basic Drive FC 101
AQ275641848264en-000101 / 132R0078| 75
Danfoss A/S © 2019.11