Drive
P18K
P22K
P30K
P37K
P45K
P55K
P75K
P90K
Intermittent (3x441–480 V) [A]
32.2
38.1
54.1
66.7
79.8
97.5
132.9
157.0
Maximum mains fuses
3.2.4.5 Recommendation of Fuses and Circuit Breakers
Estimated power loss [W], best
case/typical
(1)
412/456
475/523
733
922
1067
1133
1733
2141
Weight enclosure protection
rating IP20 [kg (lb)]
9.5 (20.9)
9.5 (20.9)
24.5 (54)
24.5 (54)
24.5 (54)
36.0
(79.4)
36.0
(79.4)
51.0
(112.4)
Efficiency [%], best case/typical
(2)
98.1/97.9
98.1/97.9
97.8
97.7
98
98.2
97.8
97.9
Output current - 50°C (122°F) ambient temperature
Continuous (3x380–440 V) [A]
34.1
38.0
48.8
58.4
72.0
74.2
102.9
123.9
Intermittent (3x380–440 V) [A]
37.5
41.8
53.7
64.2
79.2
81.6
113.2
136.3
Continuous (3x441–480 V) [A]
31.3
35.0
41.6
52.0
64.0
73.5
91.0
112.0
Intermittent (3x441–480 V) [A]
34.4
38.5
45.8
57.2
70.4
80.9
100.1
123.2
1
Applies for dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and typical control card power consump-
tions are included. For power loss data according to EN 50598-2, refer to Danfoss
website.
2
Efficiency measured at nominal current. For energy efficiency class, see
. For part load losses, see Danfoss
website.
Table 24: 3x380–480 V AC, 0.75–18.5 kW (1–25 hp), Enclosure Sizes I2–I4
Drive
PK75
P1K5
P2K2
P3K0
P4KO
P5K5
P7K5
P11K
P15K
P18K
Typical shaft output [kW]
0.75
1.5
2.2
3.0
4.0
5.5
7.5
11
15
18.5
Typical shaft output [hp]
1.0
2.0
3.0
4.0
5.0
7.5
10.0
15
20
25
Protection rating IP54
I2
I2
I2
I2
I2
I3
I3
I4
I4
I4
Maximum cable size in terminals
(mains, motor) [mm
2
(AWG)]
4 (10)
4 (10)
4 (10)
4 (10)
4 (10)
4 (10)
4 (10)
16 (6)
16 (6)
16 (6)
Output current - 40°C (104°F) ambient temperature
Continuous (3x380–440 V) [A]
2.2
3.7
5.3
7.2
9.0
12.0
15.5
23.0
31.0
37.0
Intermittent (3x380–440 V) [A]
2.4
4.1
5.8
7.9
9.9
13.2
17.1
25.3
34.0
40.7
Continuous (3x441–480 V) [A]
2.1
3.4
4.8
6.3
8.2
11.0
14.0
21.0
27.0
34.0
Intermittent (3x441–480 V) [A]
2.3
3.7
5.3
6.9
9.0
12.1
15.4
23.1
29.7
37.4
Maximum input current
Continuous (3x380–440 V) [A]
2.1
3.5
4.7
6.3
8.3
11.2
15.1
22.1
29.9
35.2
Intermittent (3x380–440 V) [A]
2.3
3.9
5.2
6.9
9.1
12.3
16.6
24.3
32.9
38.7
Continuous (3x441–480 V) [A]
1.8
2.9
3.9
5.3
6.8
9.4
12.6
18.4
24.7
29.3
Intermittent (3x441–480 V) [A]
2.0
3.2
4.3
5.8
7.5
10.3
13.9
20.2
27.2
32.2
Maximum mains fuses
See
3.2.4.5 Recommendation of Fuses and Circuit Breakers
Estimated power loss [W], best
case/typical
(1)
21/16
46/57
46/58
66/83
95/11
8
104/1
31
159/1
98
248/2
74
353/3
79
412/4
56
Specifications
Operating Guide | VLT® HVAC Basic Drive FC 101
AQ275641848264en-000101 / 132R0078| 69
Danfoss A/S © 2019.11