16-11 Power [hp]
Range:
Function:
0 hp
*
[0 - 1000
hp]
View the DC link power in hp. The value
shown is calculated on the basis of the
actual motor voltage and motor current.
16-12 Motor Voltage
Range:
Function:
0 V
*
[0 - 65535 V] View the motor voltage, a calculated value
used for controlling the motor.
16-13 Frequency
Range:
Function:
0 Hz
*
[0 - 6553.5 Hz] View the motor frequency, without
resonance dampening.
16-14 Motor current
Range:
Function:
0 A
*
[0 - 655.35 A] View the motor current measured as a
mean value, IRMS.
16-15 Frequency [%]
Range:
Function:
0 %
*
[0 - 6553.5
%]
View a 2-byte word reporting the actual
motor frequency (without resonance
dampening) as a percentage (scale
0000-4000 Hex) of
16-18 Motor Thermal
Range:
Function:
0 %
*
[0 -
100 %]
View the calculated motor temperature in
percentage of allowed maximum. At 100% a trip
will occur, if selected in
. The basis for the calculation is the ETR
function selected in
.
3.12.3 16-3* Drive Status
16-30 DC Link Voltage
Range:
Function:
0 V
*
[0 - 65535 V]
View a measured value.
16-34 Heatsink Temp.
Range:
Function:
0 °C
*
[-128 - 127 °C] View the heat sink temperature of the
frequency converter.
16-35 Inverter Thermal
Range:
Function:
0 %
*
[0 - 255 %] View the percentage of thermal load on the
frequency converter. At 100% a trip occurs.
16-36 Inv. Nom. Current
Range:
Function:
0 A
*
[0 - 655.35
A]
View the inverter nominal current, which
should match the nameplate data on the
connected motor. The data are used for
motor protection, etc.
16-37 Inv. Max. Current
Range:
Function:
0 A
*
[0 - 655.35 A] View the inverter maximum current. The
data are used for calculation of frequency
converter protection, etc.
16-38 SL Controller State
Range:
Function:
0
*
[0 - 20 ] View the actual state of the Smart Logic Controller
(SLC).
3.12.4 16-5* Ref. & Feedb.
16-50 External Reference
Range:
Function:
0 %
*
[-200 - 200
%]
View the total reference, the sum of
digital, analog, preset, bus and freeze
references.
16-52 Feedback[Unit]
Range:
Function:
0 ProcessCtrlUnit
*
[-4999 - 4999
ProcessCtrlUnit]
View the feedback
resulting from the
selection of scaling in
and
3.12.5 16-6* Inputs and Outputs
16-60 Digital Input
Range:
Function:
0
*
[0 -
65535 ]
View actual state of the digital inputs 18, 19, 27
and 29.
Bit 0
Unused
Bit 1
Unused
Bit 2
Digital input term. 29
Bit 3
Digital input term. 27
Bit 4
Digital input term. 19
Bit 5
Digital input term. 18
Bit 6~15
Unused
Table 3.8 Bits Definition
Parameters
VLT
®
HVAC Basic Drive FC 101 Programming Guide
MG18B302 - Rev. 2013-09-02
71
3
3