5.
Reconnect the mains supply - the frequency
converter is now reset.
Except the following parameters:
15-00 Operating hours to 15-05 Over Volt's
15-4* Drive identification parameters
2 finger initialisation
1.
Power off the frequency converter.
2.
Press [OK] and [Menu].
3.
Power up the frequency converter while still
pressing the keys above for 10 s.
4.
The frequency converter is now reset, except the
following parameters:
15-4* Drive identification parameters
Initialisation of parameters is confirmed by AL80 in the
display after the power cycle.
How to Programme
VLT
®
HVAC Basic Drive FC 101 Programming Guide
MG18B302 - Rev. 2013-09-02
19