13-52 SL Controller Action
Array [20]
Option:
Function:
[18] Select ramp 1
Selects ramp 1
[19] Select ramp 2
Selects ramp 2
[22] Run
Issues a start command to the
frequency converter.
[23] Run reverse
Issues a start reverse command to the
frequency converter.
[24] Stop
Issues a stop command to the
frequency converter.
[25] Qstop
Issues a quick stop command to the
frequency converter.
[26] DC Brake
Issues a DC stop command to the
frequency converter.
[27] Coast
The frequency converter coasts
immediately. All stop commands
including the coast command stop the
SLC.
[28] Freeze output
Freezes the output frequency of the
frequency converter.
[29] Start timer 0
Starts timer 0, see
for further description.
[30] Start timer 1
Starts timer 1, see
for further description.
[31] Start timer 2
Starts timer 2, see
for further description.
[32] Set digital out A
low
Any output with ‘digital output 1’
selected is low (off).
[33] Set digital out B
low
Any output with ‘digital output 2’
selected is low (off).
[34] Set digital out C
low
Any output with ‘digital output 3’
selected is low (off).
[35] Set digital out D
low
Any output with ‘digital output 4’
selected is low (off).
[38] Set digital out A
high
Any output with ‘digital output 1’
selected is high (closed).
[39] Set digital out B
high
Any output with ‘digital output 2’
selected is high (closed).
[40] Set digital out C
high
Any output with ‘digital output 3’
selected is high (closed).
[41] Set digital out D
high
Any output with ‘digital output 4’
selected is high (closed).
[60] Reset Counter A
Resets Counter A to zero.
[61] Reset Counter B
Resets Counter B to zero.
[70] Start Timer 3
Starts timer 3, see
for further description.
13-52 SL Controller Action
Array [20]
Option:
Function:
[71] Start Timer 4
Starts timer 4, see
for further description.
[72] Start Timer 5
Starts timer 5, see
for further description.
[73] Start Timer 6
Starts timer 6, see
for further description.
[74] Start Timer 7
Starts timer 7, see
for further description.
Parameters
VLT
®
HVAC Basic Drive FC 101 Programming Guide
64
MG18B302 - Rev. 2013-09-02