6-29 Terminal 54 Mode
[1]
Voltage
6-25 T54 high Feedback
0050
Hz
20-94 PI integral time
0020.00
s
Current
Voltage
This dialog is forced to be set to
[1] Analog input 54
27
28
29
30
31
32
33
34
20-00 Feedback 1 source
[1]
Analog input 54
3-10 Preset reference [0]
0.00
3-03 Max Reference
50.00
3-02 Min Reference
0.00
Asynchronous Motor
1-73 Flying Start
[0]
No
1-22 Motor Voltage
0050
V
1-24 Motor current
04.66
A
1-25 Motor nominal speed
1420
RPM
3-41 Ramp 1 ramp-up time
0003
s
3-42 Ramp1 ramp-down time
0003
s
5
6
7
8
9
18
19
20
21
22
22a
23
24
25
26
35
36
37
38
39
40
0-06 Grid Type
4-12 Motor speed low limit
0016
Hz
4-13 Motor speed high limit
0050
Hz
130BC402.10
1-20 Motor Power
1.10
kW
1-23 Motor frequency
0050
Hz
6-22 T54 Low Current
A
6-24 T54 low Feedback
0016
Hz
6-23 T54 high Current
13.30
A
6-25 T54 high Feedback
0050
0.01
s
20-81 PI Normal/Inverse Control
[0]
Normal
20-83 PI Normal/Inverse Control
0050
Hz
20-93 PI Proportional Gain
00.50
1-29 Automatic Motor Adaption
[0]
Off
6-20 T54 low Voltage
0050
V
6-24 T54 low Feedback
0016
Hz
6-21 T54 high Voltage
0220
V
6-26 T54 Filter time const.
1-00 Configuration Mode
[3]
Closed Loop
3
0-03 Regional Settings
[0]
Power kW/50 Hz
1
3-16 Reference Source 2
[0]
No Operation
22b
1-10 Motor Type
[0]
Asynchronous
4
2
[0]
200-240V/50Hz/Delta
1-30 Stator resistance
0.65
Ohms
1-25 Motor nominal speed
3000
RPM
1-24 Motor Current
3.8
A
1-26 Motor Cont. Rated Torque
5.4
Nm
1-37 d-axis inductance(Ld)
5
mH
4-19 Max Ouput Frequency
0065
Hz
1-40 Back EMF at 1000 rpm
57
V
10
11
12
13
14
15
16
17
PM motor
1-39 Motor poles
8
%
04.66
Hz
MotorType = Asynchronous
MotorType = PM Motor
Illustration 2.5 Closed Loop Set-up Wizard
How to Programme
VLT
®
HVAC Basic Drive FC 101 Programming Guide
14
MG18B302 - Rev. 2013-09-02
2
2