5-53 Term. 29 High Ref./Feedb. Value
Range:
Function:
50
*
Size
related
*
[-4999 - 4999 ]
[-999999.999 -
999999.999
ReferenceFeed-
backUnit]
Enter the high reference value
[RPM] for the motor shaft
speed and the high feedback
value, see also
5-58 Term. 33
High Ref./Feedb. Value
. Select
terminal 29 as a digital input
(
5-02 Terminal 29 Mode
=
[0]
input
(default) and
5-13 Terminal 29 Digital Input
=
applicable value).
3.6.6 5-9* Bus Controlled
This parameter group selects digital and relay outputs via
a fieldbus setting.
5-90 Digital & Relay Bus Control
Range:
Function:
0
*
[0 -
0xFFFFFFFF ]
This parameter holds the state of the digital
outputs and relays that is controlled by bus.
A logical '1' indicates that the output is
high or active.
A logical '0' indicates that the output is low
or inactive.
Bit 0 - 3
Reserved
Bit 4
Relay 1 output terminal
Bit 5
Relay 2 output terminal
Bit 6 - 23
Reserved
Bit 24
Terminal 42 Digital Output
Bit 25
Terminal 45 Digital Output
Bit 26 - 31
Reserved
Table 3.5 Bit Functions
Parameters
VLT
®
HVAC Basic Drive FC 101 Programming Guide
MG18B302 - Rev. 2013-09-02
47