1-82 Min Speed for Function at Stop [Hz]
Range:
Function:
0 Hz
*
[0 - 20 Hz] Set the output frequency at which to
activate
.
1-90 Motor Thermal Protection
Option:
Function:
Using ETR (Electronic Thermal Relay), the
motor temperature is calculated based on
frequency, speed and time. Danfoss
recommends using the ETR function, if a
thermistor is not present. The functionality is
the same for asynchronous motors and PM
motors.
NOTICE
ETR calculation is based on motor data
from group
1-2* Motor Data
.
[0] No
protection
Disables temperature monitoring.
[1] Thermistor
warning
A thermistor gives a warning if upper limit of
motor temperature range is exceeded,
[2] Thermistor
trip
A thermistor gives an alarm and makes the
frequency converter trip if upper limit of
motor temperature range is exceeded.
[3] ETR warning
1
If calculated upper limit of motor temperature
range is exceeded, a warning occurs.
[4] ETR trip 1
If 90% of calculated upper limit of motor
temperature range is exceeded, an alarm
occurs and frequency converter trips.
1-93 Thermistor Source
Option:
Function:
NOTICE
This parameter cannot be adjusted
while the motor is running.
NOTICE
Digital input should be set to
[0] PNP -
Active at 24 V
in
Select the input which the thermistor (PTC
sensor) should be connected. When using an
analog input, the same analog cannot be used
as a reference in
3-15 Reference Resource 1
to
3-17 Reference Resource 3
.
[0]
*
None
[1]
Analog
input AI53
[6]
Digital
input DI29