WARNING
UNINTENDED START
When the frequency converter is connected to AC mains,
or DC power supply, the motor may start at any time.
Unintended start during programming, service, or repair
work can result in death, serious injury, or property
damage. The motor can start with an external switch, a
serial bus command, an input reference signal from the
LCP, or after a cleared fault condition.
To prevent unintended motor start:
•
Disconnect the frequency converter from mains.
•
Press [Off/Reset] on the LCP, before
programming parameters.
•
The frequency converter, motor, and any driven
equipment must be fully wired and assembled
when the frequency converter is connected to
AC mains, or DC power supply.
4.2.1 Uploading Data to the LCP
1.
Press [Off] to stop the motor before uploading or
downloading data.
2.
Go to
parameter 0-50 LCP Copy
.
3.
Press [OK].
4.
Select
[1] All to LCP
.
5.
Press [OK]. A progress bar shows the uploading
process.
6.
Press [Hand On] or [Auto On] to return to normal
operation.
4.2.2 Downloading Data from the LCP
1.
Press [Off] to stop the motor before uploading or
downloading data.
2.
Go to
parameter 0-50 LCP Copy
.
3.
Press [OK].
4.
Select
[2] All from LCP
.
5.
Press [OK]. A progress bar shows the
downloading process.
6.
Press [Hand On] or [Auto On] to return to normal
operation.
4.3 Restoring Default Settings
NOTICE
Initialization restores the unit to factory default settings.
Any programming, motor data, localization, and
monitoring records are lost. Uploading data to the LCP
provides a back-up before initialization.
Restoring the frequency converter parameter settings back
to default values is done by initialization of the frequency
converter. Initialization can be carried out via
parameter 14-22 Operation Mode
or manually.
•
Initialization using
parameter 14-22 Operation
Mode
does not change frequency converter data
such as hours run, serial communication
selections, personal menu settings, fault log,
alarm log, and other monitoring functions.
•
Using
parameter 14-22 Operation Mode
is
recommended.
•
Manual initialization erases all motor,
programming, localization, and monitoring data
and restores factory default settings.
4.3.1 Recommended Initialization
1.
Press [Main Menu] twice to access parameters.
2.
Scroll to
parameter 14-22 Operation Mode
.
3.
Press [OK].
4.
Scroll to
Initialisation
.
5.
Press [OK].
6.
Remove power to the unit and wait for the
display to turn off.
7.
Apply power to the unit.
Default parameter settings are restored during start-up.
This may take slightly longer than normal.
8.
Alarm 80 is shown.
9.
Press [Reset] to return to operation mode.
4.3.2 Manual Initialization
1.
Remove power to the unit and wait for the
display to turn off.
2.
Press and hold [Status], [Main Menu], and [OK] at
the same time and apply power to the unit.
Factory default parameter settings are restored during
start-up. This may take slightly longer than normal.
Manual initialization does not reset the following
frequency converter information:
•
Parameter 15-00 Operating hours
•
Parameter 15-03 Power Up's
•
Parameter 15-04 Over Temp's
•
Parameter 15-05 Over Volt's
User Interface
Operating Guide
MG04F402
Danfoss A/S © 05/2016 All rights reserved.