1.
2.
-
-
-
3.
-
-
-
-
-
1.
2.
-
e3
0b
h5
14
.1
0
Illustration 59: Adding a Servo Drive to the Project in V4.x
6.10.10 Importing PSM 510, DAM 510 and ACM 510 into Automation Studio™
N O T I C E
For each physical Power Supply Module (PSM 510), Decentral Access Module (DAM 510), and Auxiliary Capacitors Module
(ACM 510), add 1 entry to the
Physical View
of Automation Studio
™
.
6.10.10.1 Version V3.0.90
Procedure
Select the menu entry [Tools
→
Import Fieldbus Device...].
Select the XDD file for the PSM 510, DAM 510, or ACM 510 from its location on the hard drive. This import only needs to be
done once per project. The device is then known to Automation Studio
™
.
Power Supply Module (PSM 510):
0x0300008D_PSM.xdd
Decentral Access Module (DAM 510):
0x0300008D_DAM.xdd
Auxiliary Capacitors Module (ACM 510):
0x0300008D_ACM.xdd
Now add the PSM 510, DAM 510, or ACM 510 to the Ethernet POWERLINK
®
interface of the controller in the
Physical View
:
Right-click on the controller in the
Physical View
and select [Open POWERLINK].
Right-click on the interface and select
Insert...
.
In the
Select controller module
window, select the PSM 510, DAM 510, or ACM 510 in the group
POWERLINK Devices
.
Click on
Next
.
In the next window, enter the node number of the PSM 510, DAM 510, or ACM 510.
e3
0b
h5
15
.1
0
Illustration 60: 1 PSM 510, 1 DAM 510, and 2 ISD 510 Servo Drives Added to the Ethernet POWERLINK
®
Interface in V3.0.90
6.10.10.2 Version V4.x
Procedure
Select the menu entry [Tools
→
Import Fieldbus Device...].
Select the XDD file for the PSM 510, DAM 510, or ACM 510 from its location on the hard drive. The device is then known to
Automation Studio
™
.
AQ262449648484en-000101 / 175R1135
92 | Danfoss A/S © 2020.08
Commissioning
VLT® Servo Drive System ISD 510/DSD 510
Operating Guide