5-40 Function Relay
Array (Relay 1 [0], Relay 2 [1])
Select options to define the function of the relays.
The selection of each mechanical relay is realized in an array
parameter.
Option:
Function:
clockwise (the logical product of
the status bits
running
AND
reverse
).
[165]
Local ref.
active
The output is high when
parameter 3-13 Reference Site
=
[2]
Local
or when
parameter 3-13 Reference Site
=
[0]
Linked to hand auto
at the same
time as the LCP is in [Hand on]
mode.
[166]
Remote ref.
active
The output is high when
parameter 3-13 Reference Site
is set
to
[0] Linked to Hand / Auto
or
[1]
Remote
, while the LCP is in
Auto on
mode.
[167]
Start
command
activ
The output is high when there is an
active start command (that is, via
digital input, bus connection, [Hand
on] or [Auto on], and no stop
command is active.
[168]
Drive in hand
mode
The output is high when the
frequency converter is in
Auto on
mode (as indicated by the LED light
above [Hand on].
[169]
Drive in auto
mode
The output is high when the
frequency converter is in
Auto on
mode (as indicated by the LED light
above [Auto on].
5-41 On Delay, Relay
Array [2], (Relay 1 [0], Relay 2 [1])
Range:
Function:
0.01 s
*
[0 - 600 s]
Enter the delay of the relay cut in
time. Select one of 2 internal
mechanical relays in an array
function. See
for
details.
Selected
Event
Relay
output
Selected
Event
Relay
output
On Delay
P 5-41
On Delay
P 5-41
Off Delay
P 5-42
130BA171.10
Illustration 3.5 On Delay, Relay
5-42 Off Delay, Relay
Array[2]: Relay1[0], Relay2[1]
Range:
Function:
0.01 s
*
[0 - 600 s]
Enter the delay of the relay cut out
time. Select one of 2 internal
mechanical relays in an array
function. See
for
details. If the selected event
condition changes before a delay
timer expires, the relay output is
unaffected.
Selected
Event
Relay
output
On Delay
P 5-41
Off Delay
P 5-42
130BA172.10
Illustration 3.6 Off Delay, Relay
If the selected event condition changes before the on
delay or off delay timer expires, the relay output is
unaffected.
3.6.4 5-5* Pulse Input
The pulse input parameters are used to define an
appropriate window for the impulse reference area by
configuring the scaling and filter settings for the pulse
inputs. Input terminals 29 or 33 act as frequency reference
inputs. Set terminal 29 (
parameter 5-13 Terminal 29 Digital
Input
) or terminal 33 (
parameter 5-15 Terminal 33 Digital
Parameters
VLT
®
Compressor Drive CDS 803
34