3.5.1.3 Ring/Redundant Topology

130BE801.10

Illustration 3.4 Ring/Redundant Topology

Ring topology can increase the availability of an Ethernet
network.

For ring topology:

Install a special switch (redundancy manager)
between the BMS controller and the frequency
converters.

Configure the redundancy manager switch to
clearly define the ports that connect to the ring.

When the ring is closed, the main redundancy manager
tests the ring for detects. If the redundancy manager
detects a fault in the ring, it reconfigures the ring into 2
lines instead. The transition time from ring topology into 2
lines can vary from 200 ms up to several seconds
depending on the components installed in the ring. Set
the timing of the BMS controller to ensure that the
transition time does not lead to a timeout fault.

NOTICE

For ring/redundant topology, ensure that the redundancy
manager switch supports the detection of loss of line
topology. The switch inside the BACnet/IP interface does
not support this detection, as the redundancy manager
has to perform this task.

3.5.1.4 Recommended Design Rules

Pay special attention to active network
components when designing an Ethernet
network.

For line topology, a small delay is added with
each additional switch in the line. For more
information, see 

Table 3.1

.

Do not connect more than 32 frequency
converters in series. To prevent unstable or faulty
communication, set the timing, if this limit is
exceeded.

AutomationDrive

VLT

AutomationDrive

VLT

AutomationDrive

VLT

AutomationDrive

VLT

AutomationDrive

VLT

AutomationDrive

VLT

AutomationDrive

VLT

AutomationDrive

VLT

AutomationDrive

VLT

AutomationDrive

VLT

AutomationDrive

VLT

AutomationDrive

VLT

AutomationDrive

VLT

AutomationDrive

VLT

Max. 32 drives

130BE802.10

Illustration 3.5 Recommended Design Rules

3.6  Mounting

1.

Check whether the fieldbus option is already
mounted in the frequency converter. If the option
is already mounted, go to step 6.

2.

Remove the LCP or blind cover from the
frequency converter.

3.

Use a screwdriver to remove the front cover and
the LCP cradle.

4.

Mount the fieldbus option with the Ethernet port
facing upwards for top cable entry (see

Illustration 3.7

), or with the Ethernet port facing

downwards for bottom cable entry (see

Illustration 3.8

).

5.

Remove the knockout plate from the new LCP
cradle.

6.

Mount the new LCP cradle.

Installation

VLT

®

 BACnet/IP MCA 125

8

Danfoss A/S © 05/2016 All rights reserved.

MG92K102

3

3

Содержание VLT BACnet/IP MCA 125

Страница 1: ...MAKING MODERN LIVING POSSIBLE Installation Guide VLT BACnet IP MCA 125 VLT HVAC Drive FC 102 vlt drives danfoss com...

Страница 2: ......

Страница 3: ...3 3 Grounding 6 3 4 Cable Routing 6 3 5 Topology 7 3 5 1 Topology Types 7 3 5 1 1 Star Topology 7 3 5 1 2 Line Topology 7 3 5 1 3 Ring Redundant Topology 8 3 5 1 4 Recommended Design Rules 8 3 6 Moun...

Страница 4: ...configuring the system controlling the frequency converter parameter access programming troubleshooting and some typical application examples Supplementary publications and manuals are available from...

Страница 5: ...er PLC Programmable logic controller TCP Transmission control protocol Table 1 1 Symbols and Abbreviations Conventions Numbered lists indicate procedures Bullet lists indicate other information and de...

Страница 6: ...DC supply or load sharing the motor may start at any time Unintended start during programming service or repair work can result in death serious injury or property damage The motor can start with an...

Страница 7: ...injury Ensure that only trained and qualified personnel perform installation start up and maintenance Ensure that electrical work conforms to national and local electrical codes Follow the procedures...

Страница 8: ...ctrical contact between the cable screen and the frequency converter enclosure or ground is not allowed in Ethernet installations The RJ45 connector of the Ethernet interface provides an electrical pa...

Страница 9: ...thernet switch When the update time is too short the delay can lead to a timeout in the BMS Set the update time as shown in Table 3 1 The numbers given are typical values and can vary from installatio...

Страница 10: ...active network components when designing an Ethernet network For line topology a small delay is added with each additional switch in the line For more information see Table 3 1 Do not connect more th...

Страница 11: ...t Facing Upward A1 A3 Enclosures 130BD925 10 Illustration 3 8 Option Mounted with the Ethernet Port Facing Downward A4 A5 B C D E F Enclosures 130BD910 10 2 4 3 M12 PIN RJ45 8 1 1 Signal M12 PIN RJ45...

Страница 12: ...providing galvanic isolation 3 7 2 Wiring Procedures Wiring procedure for enclosure types A1 A3 1 Mount the pre configured cable wires with the connectors on the fieldbus option For A1 and A2 enclosur...

Страница 13: ...the metal base plate using the springs see Illustration 3 12 3 Tie down the cable and route it with other control wires inside the unit see Illustration 3 12 130BC527 10 Illustration 3 12 Wiring for E...

Страница 14: ...Control Timeout Time Parameter 8 70 BACnet Device Instance Parameter 12 71 BACnet Datalink If BACnet IP is used the following parameters must be set correctly Parameter 12 00 IP Address Assignment Par...

Страница 15: ...MS Module status Reflects the activity on the BACnet IP stack NS1 Network status 1 Reflects the activity on Ethernet port 1 NS2 Network status 2 Reflects the activity on Ethernet port 2 Table 4 1 LED...

Страница 16: ...Status to verify presence of the link Use parameter 12 11 Link Duration to verify that the link is steadily present The parameter shows the duration of the present link and is preset to 00 00 00 00 w...

Страница 17: ...6 H High voltage 4 I Installation EMC compliant 6 Intended use 2 Items supplied 2 L Leakage current 5 LED 3 Line topology 7 Load sharing 4 M Motor wiring 6 Mounting 8 N Network cabling 12 Q Qualified...

Страница 18: ...ucts already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed All trademarks in this material are property of the resp...

Отзывы: