3.5  Topology

3.5.1 Topology Types

The BACnet/IP MCA 125 option features a built-in Ethernet
switch with 2 Ethernet RJ45 connectors. Where the
enclosure protection rating if higher than IP2x, the
frequency converter may be equipped with two M12
connectors instead.
The module enables the connection of several BACnet/IP
options in a line topology as an alternative to a traditional
star topology.

The 2 ports are equal. If only 1 connector is used, either
port can be used.

3.5.1.1 Star Topology

130BE799.10

Illustration 3.2 Star Topology

3.5.1.2 Line Topology

In many installations, line topology enables simpler cabling
and the use of smaller or fewer Ethernet switches. The
BACnet/IP interface supports line topology with its 2 ports
and built-in Ethernet switch.
When line topology is used, take precautions to avoid
timeout in the BMS when more than 8 frequency
converters are installed in series. Each frequency converter
in the network adds a small delay to the communication
due to the built-in Ethernet switch. When the update time
is too short, the delay can lead to a timeout in the BMS.

Set the update time as shown in 

Table 3.1

. The numbers

given are typical values and can vary from installation to
installation.

Numbers of frequency converters

connected in series

Minimum update time [ms]

<8

2

8–16

4

16–32

8

>32

Large jitter can occur.

Table 3.1 Minimum Update Time

AutomationDrive

VLT

AutomationDrive

VLT

AutomationDrive

VLT

AutomationDrive

VLT

AutomationDrive

VLT

AutomationDrive

VLT

AutomationDrive

VLT

130BE800.10

Illustration 3.3 Line Topology

NOTICE

In line topology, activate the built-in switch by powering
all frequency converters, either by mains or a 24 V DC
option card.

NOTICE

Installing frequency converters of different power sizes in
line topology may result in unwanted power-off behavior
when using control word timeout (

parameter 8-02 Control

Word Source

 to 

parameter 8-06 Reset Control Word

Timeout

). Mount the frequency converters with the

longest discharge time first in the line topology. In
normal operation, the frequency converters with bigger
power sizes have a longer discharge time.

Installation

Installation Guide

MG92K102

Danfoss A/S © 05/2016 All rights reserved.

7

3

3

Содержание VLT BACnet/IP MCA 125

Страница 1: ...MAKING MODERN LIVING POSSIBLE Installation Guide VLT BACnet IP MCA 125 VLT HVAC Drive FC 102 vlt drives danfoss com...

Страница 2: ......

Страница 3: ...3 3 Grounding 6 3 4 Cable Routing 6 3 5 Topology 7 3 5 1 Topology Types 7 3 5 1 1 Star Topology 7 3 5 1 2 Line Topology 7 3 5 1 3 Ring Redundant Topology 8 3 5 1 4 Recommended Design Rules 8 3 6 Moun...

Страница 4: ...configuring the system controlling the frequency converter parameter access programming troubleshooting and some typical application examples Supplementary publications and manuals are available from...

Страница 5: ...er PLC Programmable logic controller TCP Transmission control protocol Table 1 1 Symbols and Abbreviations Conventions Numbered lists indicate procedures Bullet lists indicate other information and de...

Страница 6: ...DC supply or load sharing the motor may start at any time Unintended start during programming service or repair work can result in death serious injury or property damage The motor can start with an...

Страница 7: ...injury Ensure that only trained and qualified personnel perform installation start up and maintenance Ensure that electrical work conforms to national and local electrical codes Follow the procedures...

Страница 8: ...ctrical contact between the cable screen and the frequency converter enclosure or ground is not allowed in Ethernet installations The RJ45 connector of the Ethernet interface provides an electrical pa...

Страница 9: ...thernet switch When the update time is too short the delay can lead to a timeout in the BMS Set the update time as shown in Table 3 1 The numbers given are typical values and can vary from installatio...

Страница 10: ...active network components when designing an Ethernet network For line topology a small delay is added with each additional switch in the line For more information see Table 3 1 Do not connect more th...

Страница 11: ...t Facing Upward A1 A3 Enclosures 130BD925 10 Illustration 3 8 Option Mounted with the Ethernet Port Facing Downward A4 A5 B C D E F Enclosures 130BD910 10 2 4 3 M12 PIN RJ45 8 1 1 Signal M12 PIN RJ45...

Страница 12: ...providing galvanic isolation 3 7 2 Wiring Procedures Wiring procedure for enclosure types A1 A3 1 Mount the pre configured cable wires with the connectors on the fieldbus option For A1 and A2 enclosur...

Страница 13: ...the metal base plate using the springs see Illustration 3 12 3 Tie down the cable and route it with other control wires inside the unit see Illustration 3 12 130BC527 10 Illustration 3 12 Wiring for E...

Страница 14: ...Control Timeout Time Parameter 8 70 BACnet Device Instance Parameter 12 71 BACnet Datalink If BACnet IP is used the following parameters must be set correctly Parameter 12 00 IP Address Assignment Par...

Страница 15: ...MS Module status Reflects the activity on the BACnet IP stack NS1 Network status 1 Reflects the activity on Ethernet port 1 NS2 Network status 2 Reflects the activity on Ethernet port 2 Table 4 1 LED...

Страница 16: ...Status to verify presence of the link Use parameter 12 11 Link Duration to verify that the link is steadily present The parameter shows the duration of the present link and is preset to 00 00 00 00 w...

Страница 17: ...6 H High voltage 4 I Installation EMC compliant 6 Intended use 2 Items supplied 2 L Leakage current 5 LED 3 Line topology 7 Load sharing 4 M Motor wiring 6 Mounting 8 N Network cabling 12 Q Qualified...

Страница 18: ...ucts already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed All trademarks in this material are property of the resp...

Отзывы: