3.10 Checking Network Cabling
NOTICE
After installing the BACnet/IP interface, be aware of the
following parameter settings:
•
Parameter 8-01 Control Site
:
[2] Control word only
or
[0] Digital and control word
•
Parameter 8-02 Control Word Source
:
[3] Option
A
.
•
Parameter 8-03 Control Timeout Time
.
•
Parameter 8-70 BACnet Device Instance
.
•
Parameter 12-71 BACnet Datalink
.
If BACnet/IP is used the following parameters must be
set correctly:
•
Parameter 12-00 IP Address Assignment
.
•
Parameter 12-01 IP Address
(if
parameter 12-00 IP
Address Assignment
is set to
[0] MANUAL
).
•
Parameter 12-02 Subnet Mask
(if
parameter 12-00 IP Address Assignment
is set to
[0] MANUAL
).
Installation
VLT
®
BACnet/IP MCA 125
12
Danfoss A/S © 05/2016 All rights reserved.
MG92K102
3
3