Technical data
Basic unit without extensions
Main supply (L1, L2, L3)
Supply voltage
200-240 V AC
380-500 V AC
525-600 V AC
525-690 V AC
Supply frequency
50/60 Hz
Displacement power factor
(cos ф) near unity
> 0.98
Switching on input supply
L1, L2, L3
1-2 times/min.
Output data (T1, T2, T3)
Output voltage
0-100% of supply voltage
Output frequency
0-590 Hz
Switching on output
Unlimited
Ramp times
0.01-3600 s
Digital inputs
Programmable digital inputs
6*
Changeable to digital output
2 (terminal 27, 29)
Logic
PNP or NPN
Voltage level
0-24 V DC
Maximum voltage on input
28 V DC
Input resistance, Ri
Approx. 4 kΩ
Scan interval
5 ms
* Two of the inputs can be used as digital outputs
Analog inputs
Analog inputs
2
Modes
Voltage or current
Voltage level
0 to +10 V (scaleable)
Current level
0/4 to 20 mA (scaleable)
Accuracy of analog inputs
Max. error: 0.5% of full scale
Pulse inputs
Programmable pulse inputs
2*
Voltage level
0-24 V DC (PNP positive logic)
Pulse input accuracy
(0.1-1 kHz)
Max. error: 0.1% of full scale
* Two of the digital inputs can be used for pulse inputs.
Digital outputs
Programmable
digital/pulse outputs
2
Voltage level at
digital/frequency output
0-24 V DC
Max. output current
(sink or source)
40 mA
Maximum output frequency
0-32 kHz
Accuracy on frequency output
Max. error: 0.1% of full scale
Analog outputs
Programmable
analog outputs
1
Current range at
analog output
0/4-20 mA
Max. load to common at
analog output (clamp 30)
500 Ω
Accuracy on analog output
Max. error: 0.5 % of full scale
Control card
USB interface
1.1 (Full Speed)
USB plug
Type “B”
RS485 interface
Up to 115 kBaud
Max. load (10 V)
15 mA
Max. load (24 V)
200 mA
Relay outputs
Programmable relay outputs
2
Max. terminal load (AC)
on 1-3 (NC), 1-2 (NO),
4-6 (NC) power card
240 V AC, 2 A
Max. terminal load (AC -1) on
4-5 (NO) power card
400 V AC, 2 A
Min. terminal load on
1-3 (NC), 1-2 (NO),
4-6 (NC), 4-5 (NO)
power card
24 V DC 10 mA, 24 V AC 20 mA
Surroundings/external
Ingress protection class
IP: 00/20/21/54/55/66
UL Type: Chassis/1/12/3R/4X
Vibration test
0.7 g
Max. relative humidity
5-95% (IEC 721-3-3); Class 3K3
(non-condensing) during operation
Ambient temperature
Max. 50 °C without derating
Galvanic isolation of all
I/O supplies according to PELV
Aggressive environment
Designed for 3C3 (IEC 60721-3-3)
Ambient temperature
– Operating temperature range is -25 °C to 50 °C without derating
Max 55 °C with derating
Fieldbus communication
Standard built-in:
FC Protocol
N2 Metasys
FLN Apogee
Modbus RTU
Optional:
VLT® PROFIBUS DP V1 MCA 101
VLT® DeviceNet MCA 104
VLT® CANopen MCA 105
VLT® 3000 PROFIBUS Converter MCA 113
VLT® 5000 PROFIBUS Converter MCA 114
VLT® PROFINET MCA 120
VLT® EtherNet/IP MCA 121
VLT® Modbus TCP MCA 122
VLT® POWERLINK MCA 123
VLT® EtherCAT MCA 124
VLT® 5000 DeviceNet Converter MCA 194
Protection mode for longest possible up-time
– Electronic motor thermal protection against overload
– Protection against overtemperature
– The AC drive is protected against short circuits
on motor terminals R, S, T
– The AC drive is protected against ground faults
on motor terminals U, V, W
– Protection against mains phase loss
– Real-Time Clock with battery backup
– Advanced data logging using real-time stamps
– Predictive maintenance
– Preventive maintenance
– D-option VLT® Real-time Clock Option MCB 117
Agency approvals
29
| Content | Danfoss Drives · DKDD.PB.302.A8.02