39
| Content | Danfoss Drives · DKDD.PB.302.A8.02
[T5]
6 x 380-500 V AC – high overload
High overload (150% 1 min/10 min)
Enclosure size
Type
code
Output current
Typical shaft
output power
Conti-
nuous
input
current
Esti-
mated
power
loss
Protection rating [IEC/UL]
(3 x 380-440 V)
(3 x 441-500 V)
IP21/Type 1
IP54/Type 12
FC-302
Con. I
N
Inter. I
MAX
(60 s)
Con. I
N
Inter. I
MAX
(60 s)
kW @ 400 V
Hp @ 460 V
[A]
[W]
AC
drive
+
options
AC
drive
+
options
P250
480
720
443
665
250
350
472
5164
F8
F9
F8
F9
P315
600
900
540
810
315
450
590
6960
F8
F9
F8
F9
P355
658
987
590
885
355
500
647
7691
F8
F9
F8
F9
P400
695
1043
678
1017
400
550
684
8178
F8
F9
F8
F9
P450
800
1200
730
1095
450
600
779
9492
F10
F11
F10
F11
P500
880
1320
780
1170
500
650
857
10631
F10
F11
F10
F11
P560
990
1485
890
1335
560
750
964
11263
F10
F11
F10
F11
P630
1120
1680
1050
1575
630
900
1090
13172
F10
F11
F10
F11
P710
1260
1890
1160
1740
710
1000
1227
14967
F12
F13
F12
F13
P800
1460
2190
1380
2070
800
1200
1422
16392
F12
F13
F12
F13
[T5]
6 x 380-500 V AC – normal overload
Normal overload (110% 1 min/10 min)
Enclosure size
Type
code
Output current
Typical shaft
output power
Conti-
nuous
input
current
Esti-
mated
power
loss
Protection rating [IEC/UL]
(3 x 380-440 V)
(3 x 441-500 V)
IP21/Type 1
IP54/Type 12
FC-302
Con. I
N
Inter. I
MAX
(60 s)
Con. I
N
Inter. I
MAX
(60 s)
kW @ 400 V
Hp @ 460 V
[A]
[W]
AC
drive
+
options
AC
drive
+
options
P250
600
660
540
594
315
450
590
6790
F8
F9
F8
F9
P315
658
724
590
649
355
500
647
7701
F8
F9
F8
F9
P355
745
820
678
746
400
600
733
8879
F8
F9
F8
F9
P400
800
880
730
803
450
600
787
9670
F8
F9
F8
F9
P450
880
968
780
858
500
650
857
10647
F10
F11
F10
F11
P500
990
1089
890
979
560
750
964
12338
F10
F11
F10
F11
P560
1120
1232
1050
1155
630
900
1090
13201
F10
F11
F10
F11
P630
1260
1386
1160
1276
710
1000
1227
15436
F10
F11
F10
F11
P710
1460
1606
1380
1518
800
1200
1422
18084
F12
F13
F12
F13
P800
1720
1892
1530
1683
1000
1350
1675
20358
F12
F13
F12
F13
Electrical data and dimensions – VLT® 12-Pulse