440–480 V, 60 Hz
I
AHF,N
Typical Motor Used [HP]
Danfoss ordering number
Adjustable frequency drive
size
AHF 005
AHF 010
19 A
10 - 15
175G6612
175G6634
P11K
26 A
20
175G6613
175G6635
P15K
35 A
25 - 30
175G6614
175G6636
P18K, P22K
43 A
40
175G6615
175G6637
P30K
72 A
50 - 60
175G6616
175G6638
P37K - P45K
101A
75
175G6617
175G6639
P55K
144 A
100 - 125
175G6618
175G6640
P75K
180 A
150
175G6619
175G6641
P90
217 A
200
175G6620
175G6642
P110
289 A
250
175G6621
175G6643
P132 - P160
324 A
300
175G6689
175G6692
370 A
350
175G6690
175G6693
P200
434 A
350
2x175G6620
2x175G6642
P250
578 A
500
2x 175G6621
2x 175G6643
P315 - P355
659 A
550-600
17 175G6621
17 175G6643
P400
Matching the adjustable frequency drive and filter is pre-calculated based on 400 V/480 V, a typical motor load (4-pole) and 110% torque.
500–525 V, 50 Hz
I
AHF,N
Typical Motor Used [kW]
Danfoss ordering number
Adjustable frequency drive
size
AHF 005
AHF 010
10 A
0.75–5.5
175G6644
175G6656
PK75 - P5K5
19 A
7.5–11
175G6645
175G6657
P7K5 - P11K
26 A
15 18.5
175G6646
175G6658
P15K - P18K
35 A
22
175G6647
175G6659
P22K
43 A
30
175G6648
175G6660
P30K
72 A
37 -45
175G6649
175G6661
P37K - P45K
101 A
55 - 75
175G6650
175G6662
P55K - P75K
144 A
90 - 110
175G6651
175G6663
P90K - P110
180 A
132
175G6652
175G6664
P132
217 A
160
175G6653
175G6665
P160
289 A
200
175G6654
175G6666
P200
324 A
250
175G6655
175G6667
P250
370 A
315
2x175G6653
2x175G6665
P315 - P400
578 A
400
2X 175G6654
2X 175G6666
P500 - P560
4 How to Order
VLT
®
AQUA Drive Design Guide
4-10
MG.20.N5.22 - VLT
®
is a registered Danfoss trademark
4
Содержание vlt aqua
Страница 4: ...Contents VLT AQUA Drive Design Guide MG 20 N5 22 VLT is a registered Danfoss trademark...
Страница 168: ...5 How to Install VLT AQUA Drive Design Guide 5 50 MG 20 N5 22 VLT is a registered Danfoss trademark 5...
Страница 186: ...6 Application Examples VLT AQUA Drive Design Guide 6 10 MG 20 N5 22 VLT is a registered Danfoss trademark 6...