Holding registers
Register Number
Description
00001-00006
Reserved
00007
Last error code from an adjustable frequency drive data object interface
00008
Reserved
00009
Parameter index*
00010-00990
000 parameter group (parameters 001 through 099)
01000-01990
100 parameter group (parameters 100 through 199)
02000-02990
200 parameter group (parameters 200 through 299)
03000-03990
300 parameter group (parameters 300 through 399)
04000-04990
400 parameter group (parameters 400 through 499)
...
...
49000-49990
4900 parameter group (parameters 4900 through 4999)
50000
Input data: Adjustable frequency drive control word register (CTW).
50010
Input data: Bus reference register (REF).
...
...
50200
Output data: Adjustable frequency drive status word register (STW).
50210
Output data: Adjustable frequency drive main actual value register (MAV).
* Used to specify the index number to be used when accessing an indexed parameter.
7.8.9 How to Control the VLT AQUA
This section describes codes which can be used in the function and data fields of a Modbus RTU message. For a complete description of all the message
fields, please refer to the section Modbus RTU Message Framing Structure.
VLT
®
AQUA Drive Design Guide
7 RS-485 Installation and Set-up
MG.20.N5.22 - VLT
®
is a registered Danfoss trademark
7-17
7