5.6 Final Set-Up and Test
To test the set-up and ensure that the adjustable frequency drive is running, follow these steps.
Step 1. Locate the motor nameplate.
NOTE!
The motor is either star- (Y) or delta-connected (
Δ
).
This information is located on the motor nameplate
data.
Step 2. Enter the motor nameplate data in this parameter list.
To access this list, first press the [QUICK MENU] key, then select “Q2
Quick Set-up”.
1.
Motor Power [kW]
or Motor Power [HP]
par. 1-20
par. 1-21
2.
Motor Voltage
par. 1-22
3.
Motor Frequency
par. 1-23
4.
Motor Current
par. 1-24
5.
Motor Nominal Speed
par. 1-25
Step 3. Activate the Automatic Motor Adaptation (AMA)
.
Performing an AMA will ensure optimum performance. The AMA measures the values from the motor model equivalent diagram.
1.
Connect terminal 27 to terminal 12 or set par. 5-12 to 'No function' (par. 5-12 [0])
2.
Activate the AMA par. 1-29.
3.
Choose between complete or reduced AMA. If an LC filter is mounted, run only the reduced AMA, or remove the LC filter during the AMA
procedure.
4.
Press the [OK] key. The display shows “Press [Hand on] to start”.
5.
Press the [Hand on] key. A progress bar indicates if the AMA is in progress.
5 How to Install
VLT
®
AQUA Drive Design Guide
5-46
MG.20.N5.22 - VLT
®
is a registered Danfoss trademark
5
Содержание vlt aqua
Страница 4: ...Contents VLT AQUA Drive Design Guide MG 20 N5 22 VLT is a registered Danfoss trademark...
Страница 168: ...5 How to Install VLT AQUA Drive Design Guide 5 50 MG 20 N5 22 VLT is a registered Danfoss trademark 5...
Страница 186: ...6 Application Examples VLT AQUA Drive Design Guide 6 10 MG 20 N5 22 VLT is a registered Danfoss trademark 6...